E54-CT1 Omron, E54-CT1 Datasheet - Page 5

TRANSFORMER CURRNT 50A E5AK/E5CK

E54-CT1

Manufacturer Part Number
E54-CT1
Description
TRANSFORMER CURRNT 50A E5AK/E5CK
Manufacturer
Omron
Datasheets

Specifications of E54-CT1

Accessory Type
Current Transformer
Input Current
50A
Transformer Mounting
Chassis
Length/height, External
25mm
Output Current
50A
Transformer Type
Current
Current Rating
50A
Mounting Type
Chassis
Supply Voltage
1000 VoltsAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
E5AK/E5CK
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
E54CT1
Z2416
J Communication Characteristics
Conforms to DeviceNet communications protocol.
For details, refer to the CompoBus/D Operation Manual and E5EK-DRT DeviceNet Process Controller User’s Manual.
Note: 1. External terminating resistor is required.
J Output Board Ratings and Characteristics
J Current Transformer Ratings
Note: 1. Use within the max heater current rating of controller table shown below.
J Heater Burnout Alarm
Note: 1. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
Connection forms
Communications baud rate
Communications media
Communications distance
Max. number of nodes
Max. number of slaves
Error control checks
Relay output
SSR output
Voltage output
Linear current output
Linear voltage output
Model
Max. continuous heater current
Dielectric strength
Vibration resistance
Weight
Accessories
Max. heater current
Heater current value display accuracy ±5% FS±1 digit max.
Heater burnout alarm setting range
Min. detection ON time
This product has been tested by ODVA’s authorized Independent Test Lab and found to comply with ODVA Conformance Test
Software Version 2.0-1.00.
A--196
2. Indicates the maximum distance between nodes.
3. The distance is less than 100 m when thin cables are used for the trunk lines.
2. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than
190 ms.
Process Controller with DeviceNet
500 kbps
250 kbps
125 kbps
5 A at 250 VAC (resistive load)
1 A at 75 to 250 VAC (resistive load)
NPN: 40 mA at 12 VDC (with short-circuit protection)
NPN: 20 mA at 24 VDC (with short-circuit protection)
PNP: 20 mA at 24 VDC (with short-circuit protection)
4 to 20 mA, permissible load impedance: 600 Ω max., resolution: approx. 2,600
0 to 20 mA, permissible load impedance: 600 Ω max., resolution: approx. 2,600
0 to 10 VDC, permissible load impedance: 1 kΩ max., resolution: approx. 2,600
0 to 5 VDC, permissible load impedance: 1 kΩ max., resolution: approx. 2,600
E54-CT1
50 amps
1,000 VAC (for 1 min)
50 Hz, 98 m/s
Approx. 11.5 g
Single-phase 50 A AC (See Note 1)
0.1 to 49.9 A (in units of 0.1 A) (See Note 2)
190 ms (See Note 3)
----
2
(10G)
E5EK- -DRT
Combination of multi-drop and T-branch connections (See Note 1)
500 kbps, 250 kbps, or 125 kbps (set using the front panel keys)
Special 5-wire cables (2 signal lines, 2 power lines, 1 shield line)
Network length (See Note 2): 100 m max. (See Note 3)
Drop line length: 6 m max.
Total drop line length: 39 m max.
Network length (See Note 2): 250 m max. (See Note 3)
Drop line length: 6 m max.
Total drop line length: 78 m max.
Network length (See Note 2): 500 m max. (See Note 3)
Drop line length: 6 m max.
Total drop line length: 156 m max.
64 nodes (including master)
63 slaves
CRC error check, duplicate node address check
E54-CT3
120 amps (See Note 1)
Approx. 50 g
Armature: 2; Plug: 2