E5ZN-2TNH03TC-FLK Omron, E5ZN-2TNH03TC-FLK Datasheet - Page 3

CONTRLR TEMP MODULAR RS-485 NPN

E5ZN-2TNH03TC-FLK

Manufacturer Part Number
E5ZN-2TNH03TC-FLK
Description
CONTRLR TEMP MODULAR RS-485 NPN
Manufacturer
Omron
Series
E5ZNr
Type
Temperature Controller, Modularr
Datasheets

Specifications of E5ZN-2TNH03TC-FLK

Output Type
Transistor
Supply Voltage
24VDC
Input Type
Thermocouple (Multiple)
Controller Type
On/Off or Proportional (PID)
Temperature Range
Selectable, Varies By Input Type
Size
DIN Rail Module
Features
DIN Rail Mount
Communications
RS-485 (CompoWay/F)
Display Type
LED Lights
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Temperature Accuracy ±
0.5%
Output Voltage Max
30VDC
Controller Output Type 1
Transistor
Mounting Type
DIN
Rohs Compliant
Yes
Thermocouple Type
J, K, T, E, L, U, N, R, S, B
Approval Bodies
CE / CSA / UL
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
E5ZN2TNH03TCFLK
Specifications
■ Ratings
Note: 1. Do not use an inverter output for the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
■ Input Range
Platinum Resistance Thermometer Models and Thermocouple Models
The applicable standards for the input types are as follows:
• K, J, T, E, N, R, S, B: JIS C1602-1995, IEC584-1
• L: Fe-CuNi, DIN 43710-1985
• U: Cu-CuNi, DIN 43710-1985
• JPt100: JIS C 1604-1989, JIS C 1606-1989
• Pt100: JIS C 1604-1997 IEC 751
Shaded parts indicate the settings at the time of purchase.
Power supply voltage
Allowable voltage range
Power consumption
Sensor input
Control output
Auxiliary output
Event input
Number of input and control points
Setting method
Control method
Other functions
Ambient operating
temperature
Ambient operating humidity
Storage temperature
Input type
Name
Setting
number
1800
1700
1600
1500
1400
1300
1200
1100
1000
−100
−200
900
800
700
600
500
400
300
200
100
2. OMRON G32A-EA Cycle Controller Unit (load impedance 352 Ω) can be used.
0
−200
850
0
Platinum resistance
thermometer models
Platinum resistance
−199.9
500.0
Pt100
1
thermometer
100.0
0.0
2
500.0
−199.9
JPt100
3
100.0
0.0
4
1300
24 VDC
85% to 110% of the rated power supply voltage
Approx. 3 W
Thermocouple: K, J, T, E, L, U, N, R, S, B
Infrared temperature sensor (ES1B series): 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C
Voltage input: 0 to 50 mV
Platinum resistance thermometer: Pt100, JPt100
Voltage output
(for driving SSR)
Transistor output
Current output
Transistor output
Linear voltage output
Contact output
Non-contact output
Input points: 2, Control points: 2
Via communications or using the Setting Display Unit (E5ZN-SDL)
2-PID or ON/OFF control
Heater burnout detection function, transfer output function
Multi-SP and RUN/STOP switching using event input
−10 to 55°C (with no icing or condensation)
For 3 years of assured use: −10 to 50°C
25% to 85%
−25 to 65°C (with no icing or condensation)
−200
0
K
−20.0 −100 −20.0
500.0
1
850
2
J
400.0
3
−200
400
4
T
−199.9
400.0
17
Output voltage: 12 VDC ±15% (PNP);
Maximum load current: 21 mA;
Equipped with short-circuit protection circuit
Maximum operational voltage: 30 VDC;
Maximum load current: 100 mA;
Residual voltage: 1.5 V max.;
Leakage current: 0.4 mA max.
Current output range: 4 to 20/0 to 20 mA DC;
Load: 350 Ω max. (See note 2.)
Sourcing
Sinking
ON: 1 kΩ max., OFF: 100 kΩ min.
Discharge current: Approx. 7 mA
ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Discharge current: Approx. 7 mA
Thermocouple
600
E
5
0
−100
850
L
6
Thermocouple models
−200
400
7
U
−199.9
400.0
Maximum operating voltage: 30 VDC;
Maximum load current: 50 mA;
Residual voltage: 1.5 V max.;
Leakage current: 0.4 mA max.
Voltage output range: 1 to 5/0 to 5 VDC;
Load: 10 kΩ min.
18
−200
1300
N
8
1700 1700
R
9
0
10
S
0
100.0
1800
11
B
10 to
70°C
12
90
0
Infrared temperature
60 to
120°C
120
13
0
sensor
115 to
165°C
165
14
0
160 to
260°C
260
15
0
Analog input
9999 or
999.9
by scaling
0 to 50 mV
1999 to
199.9 to
16
E5ZN
3