E5ZN-2TNH03TC-FLK Omron, E5ZN-2TNH03TC-FLK Datasheet - Page 5

CONTRLR TEMP MODULAR RS-485 NPN

E5ZN-2TNH03TC-FLK

Manufacturer Part Number
E5ZN-2TNH03TC-FLK
Description
CONTRLR TEMP MODULAR RS-485 NPN
Manufacturer
Omron
Series
E5ZNr
Type
Temperature Controller, Modularr
Datasheets

Specifications of E5ZN-2TNH03TC-FLK

Output Type
Transistor
Supply Voltage
24VDC
Input Type
Thermocouple (Multiple)
Controller Type
On/Off or Proportional (PID)
Temperature Range
Selectable, Varies By Input Type
Size
DIN Rail Module
Features
DIN Rail Mount
Communications
RS-485 (CompoWay/F)
Display Type
LED Lights
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Temperature Accuracy ±
0.5%
Output Voltage Max
30VDC
Controller Output Type 1
Transistor
Mounting Type
DIN
Rohs Compliant
Yes
Thermocouple Type
J, K, T, E, L, U, N, R, S, B
Approval Bodies
CE / CSA / UL
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
E5ZN2TNH03TCFLK
■ Communications
Note: The baud rate, data bit length, stop bit length, and vertical par-
■ Setting Display Unit (Order
Transmission line
connection method
Communications
method
Synchronization
method
Baud rate
Transmission code
Data bit length
(See note.)
Stop bit length (See
note.)
Error detection
Flow control
Interface
Retry function
Number of Units that
can be connected in
parallel
Power supply voltage
Allowable voltage
range
Power consumption
Display method
Ambient operating
temperature
Ambient operating hu-
midity
Storage temperature
Communications
method
Communications for-
mat
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Enclosure ratings
Memory protection
Weight
(Host Communications)
Separately)
ity can all be set independently as host communications set-
tings.
: Default setting values
24 VDC
85% to 110% of the rated power supply
voltage
Approx. 1 W
7-segment digital display and single-color
display
−10 to 55°C (with no icing or condensa-
tion)
For 3 years of assured use: −10 to 50°C
25% to 85%
−25 to 65°C (with no icing or condensa-
tion)
RS-485 (half-duplex)
Special protocol
20 MΩ min. (at 500 VDC)
1,500 VAC for 1 minute at 50 or 60 Hz (be-
tween unlike terminals of charged parts)
10 to 55 Hz, 20 m/s
and Z directions
300 m/s
±Z directions
Front panel: IP50
Rear case: IP20
Terminal case: IP00
EEPROM (non-volatile memory) (Number
of writes: 100,000)
Approx. 100 g
Mounting bracket: Approx. 10 g
RS-485 multipoint
RS-485 (2-wire, half-duplex)
Start-stop synchronization
4,800, 9,600, 19,200, or 38,400 bps
ASCII
7 or 8 bits
1 or 2 bits
Vertical parity (none, even, odd)
BCC (block check character)
None
RS-485
None
16 Units max. (32 channels)
2
max., 3 times each in ±X, ±Y, and
2
for 2 h each in X, Y,
■ Current Transformer (CT) (Order
■ Heater Burnout Alarm
Note: 1. Use the K8AC-H Digital Heater Burnout Alarm Detector for
Dielectric strength
Vibration resistance
Weight
Accessories
(E54-CT3 only)
Maximum heater
current
Input current
readout accuracy
Heater burnout
alarm setting range
Minimum detection ON
time
Separately)
2. If the heater burnout alarm setting is set to 0.0 A, the alarm
3. If the ON time for control output is less than 190 ms, heater
burnout detection of 3-phase heaters.
is always OFF, and if it is set to 50.0 A the alarm is always
ON.
burnout detection and heater current measurement will not
be performed.
1,000 VAC (1 minute)
50 Hz, 98 m/s
E54-CT1: Approx. 11.5 g
E54-CT3: Approx. 50 g
Armature (2)
Plug (2)
Single-phase, 50 A AC (See note 1.)
±5% FS ±1 digit max.
0.0 to 50.0 A (in units of 0.1 A)
(See note 2.)
190 ms (See note 3.)
2
E5ZN
5