E5ZN-2TNH03TC-FLK Omron, E5ZN-2TNH03TC-FLK Datasheet - Page 4

CONTRLR TEMP MODULAR RS-485 NPN

E5ZN-2TNH03TC-FLK

Manufacturer Part Number
E5ZN-2TNH03TC-FLK
Description
CONTRLR TEMP MODULAR RS-485 NPN
Manufacturer
Omron
Series
E5ZNr
Type
Temperature Controller, Modularr
Datasheets

Specifications of E5ZN-2TNH03TC-FLK

Output Type
Transistor
Supply Voltage
24VDC
Input Type
Thermocouple (Multiple)
Controller Type
On/Off or Proportional (PID)
Temperature Range
Selectable, Varies By Input Type
Size
DIN Rail Module
Features
DIN Rail Mount
Communications
RS-485 (CompoWay/F)
Display Type
LED Lights
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Temperature Accuracy ±
0.5%
Output Voltage Max
30VDC
Controller Output Type 1
Transistor
Mounting Type
DIN
Rohs Compliant
Yes
Thermocouple Type
J, K, T, E, L, U, N, R, S, B
Approval Bodies
CE / CSA / UL
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
E5ZN2TNH03TCFLK
■ Characteristics
Note: 1. The indication accuracy for T and N thermocouples at −100°C, and for U and L thermocouples is ±2°C ±1 digit max. There is no specifi-
Indication
accuracy
Influence of temperature
Influence of voltage
Transfer output
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Weight
Degree of protection
Memory protection
Approved standards
(See note 4.)
2. The transfer output accuracy for 0 to 4 mA when 0 to 20 mA DC is selected is ±0.5% FS +0.7 mA. The transfer output accuracy for 0 to
3. “EU” stands for “Engineering Unit.”
4. In order to satisfy the EN61326 Class A standard for conducted emissions, install a noise filter (Densei-Lambda MXB-1206-33 or equiv-
cation for the indication accuracy for the B thermocouple used at 400°C max. The indication accuracy for R and S thermocouples at
200°C max. is ±3°C ±1 digit max.
1 V when 0 to 5 VDC is selected is ±0.5% FS +0.175 V.
alent) in a DC power line as close to the E5ZN as possible.
Thermocouple: (Indicated value ±0.5% or ±1°C, whichever is greater) ±1 digit max. (See note 1.)
Platinum resistance thermometer: (Indicated value ±0.5% or ±1°C, whichever is greater) ±1 digit max. (See note
1.)
Analog input: ±0.5% or ±1 digit max.
CT input: ±5% FS ±1 digit max.
Thermocouple input (R, S, B): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: ( ±1% of PV or ±4°C, whichever is greater) ±1 digit max.
*K thermocouple at −100°C max.: ±10°C max.
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
Accuracy: ±0.5% FS (See note 2.)
0.1 to 999.9 EU (in units of 0.1 EU)
(See note 3.)
0.1 to 999.9 EU (in units of 0.1 EU)
(See note 3.)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0 to 100.0% (in units of 0.1%)
−1,999 to 9,999 (Position of decimal point depends on input type.)
500 ms
20 MΩ min. (at 500 VDC)
600 VAC for 1 minute at 50 or 60 Hz (between unlike terminals of charged parts)
10 to 55 Hz, 10 m/s
150 m/s
Temperature Controller: Approx. 90 g
Terminal Unit (18): Approx. 80 g
Terminal Unit (24): Approx. 100 g
Temperature Controller: IP00
Terminal Unit: IP00
EEPROM (non-volatile memory) (Number of write operations: 100,000)
UL File No.:
CSA File No.:
CE EMS:
EMI:
2
max., 3 times each in ±X, ±Y, and ±Z directions
ESD
REM field
Fast transient
Surge immunity EN61326, EN61000-4-5 (line to ground: 2 kV/DC power
Conducted RF
Radiated
2
for 2 h each in X, Y, and Z directions
203889-1140084
EN61326, EN61000-4-2 (4 kV/contact, 8 kV/air)
EN61326, EN61000-4-3 (10 V/m)
EN61326, EN61000-4-4 (2 kV/DC power, 1 kV/I/O)
EN61326 Class A
E200593
EN61326, EN61000-4-6 (10 V)
line to line:
1 kV/I/O
1 kV/DC power)
E5ZN
4