3G3JX-A2037 Omron Automation, 3G3JX-A2037 Datasheet - Page 22

no-image

3G3JX-A2037

Manufacturer Part Number
3G3JX-A2037
Description
Drive, Adjustable Frequency, 3-Phase, 240VAC, 5.0HP, 15.9A, RS-485 Serial , IP20
Manufacturer
Omron Automation
Type
Adjustable Frequencyr
Datasheet

Specifications of 3G3JX-A2037

Brand/series
JX
Current, Input
20 A
Function
Motor Control
Horse Power Rating
5 HP
Mounting Type
Screw
Phase
Three
Power Rating
5.0 HP
Primary Type
AC Drive
Standards
IP20
Voltage, Supply
240 VAC
Voltage, Supply Maximum
240
Lead Free Status / Rohs Status
RoHS Compliant part
■ Terminal Block Specifications
● Terminal Block Position
Note. This illustration shows the terminal block with the front cover removed
● Specifications of Main Circuit Terminals
Terminal Arrangement
3G3MX-A2002 to A2007
3G3MX-AE002 to AE004
30
Short-circuit bar
R/L1, S/L2,
U/T1, V/T2,
Terminal
P/+2, N/-
+1, P/+2
symbol
W/T3
T/L3
P/+2
RB
R/L1 S/L2 T/ L3
Multi-functional Compact Inverters SYSDRIVE
Main power supply input
terminal
Inverter output terminal
External DC reactor
terminal
External braking resistor
connection terminal
Regenerative braking unit
connection terminal
Ground terminal
Relay output terminals
RB
Terminal name
U/ T1 V/ T2 W/T3
+1
Main circuit
terminal block
Control circuit
terminal block A
Control circuit
terminal block B
P/+2
N/-
Upper
Lower
Connect the input power supply.
Connect to the motor.
Normally connected by the short-circuit bar. Remove the short-
circuit bar between +1 and P/+2 when a DC reactor is
connected.
Connect the optional braking resistor.
(If a braking torque is required)
Connect optional regenerative braking units.
(If a braking torque is required)
(if insufficient with only the built-in braking circuit)
Ground
(Connect to ground to prevent electric shock and reduce noise.)
Terminal Arrangement
3G3MX-A2015 to A2037
3G3MX-A4004 to A4037
3G3MX-AE007 to AE022
R/L1 S/L2 T/L3
+1
P/+2
Function
N/-
Short-circuit bar
U/T1 V/T2 W/T3
MX
RB
Series
RS-485 communication/
Operator selector
Upper
Lower
Frequency reference/
Run command selector
Input logic
selector
Do not remove the short-circuit bar between +1 and
P/+2 when a DC reactor is not connected.
Terminal Arrangement
3G3MX-A2055 to A2075
3G3MX-A4055 to A4075
R/L1
+1
Power supply
S/L2 T/L3 U/T1 V/T2 W/T3
P/+2
Connection example
N/-
Short-circuit bar
ELB
RB
Motor
Upper
Lower