3G3JX-A2037 Omron Automation, 3G3JX-A2037 Datasheet - Page 39

no-image

3G3JX-A2037

Manufacturer Part Number
3G3JX-A2037
Description
Drive, Adjustable Frequency, 3-Phase, 240VAC, 5.0HP, 15.9A, RS-485 Serial , IP20
Manufacturer
Omron Automation
Type
Adjustable Frequencyr
Datasheet

Specifications of 3G3JX-A2037

Brand/series
JX
Current, Input
20 A
Function
Motor Control
Horse Power Rating
5 HP
Mounting Type
Screw
Phase
Three
Power Rating
5.0 HP
Primary Type
AC Drive
Standards
IP20
Voltage, Supply
240 VAC
Voltage, Supply Maximum
240
Lead Free Status / Rohs Status
RoHS Compliant part
Digital
(con-
tact)
Analog
Open
collec-
tor out-
put
Relay
output
Analog
input
Status/
Factor
Status,
alarm,
etc.
Sensor
Terminal
symbol
MA
MB
MC
PC
TH
P1
P2
P3
P4
P5
Multi-function output
Multi-function output
common
Relay output
Relay output
common
External thermistor
input Terminal
Terminal name
Advanced General-purpose Inverters SYSDRIVE
Select 5 functions from among 51, and allocate them to terminals P1
through P5.
If an alarm code is selected in C062, terminals P1 to P3, or terminals
P1 to P4 always output an alarm factor code (e.g. Inverter trip). The
signal between each terminal and PC always corresponds to the sink
or source logic.
Common terminal for multi-function output terminals P1 to P5.
Select the desired functions from among 43 functions, and allocate
them to these terminals.
SPDT output.
By factory default, the relay output (MA, MB) contact selection (C036)
is set at NC contact between MA-MC, and NO contact between MB-
MC.
Connect an external thermistor to this terminal, to trip the Inverter
when a temperature error occurs.
The SC terminal functions as the common terminal.
[Recommended thermistor characteristics]
Allowable rated power: 100 mW min.
Impedance at temperature error: 3 kΩ
Temperature error detection level is adjustable between 0 and 9999 Ω.
Description
RX
Between each terminal
and PC
Voltage drop 4 V max. at
power-on
Max. allowable voltage:
27 V DC
Max. allowable current:
50 mA
Contact max. capacity
MA-MC
250 V AC, 2 A
(Resistance)
0.2 A (Induction)
MB-MC
250 V AC, 1 A
(Resistance)
0.2 A (Induction)
Contact min. capacity
100 V AC, 10 mA
5 V DC, 100 mA
Allowable input voltage
range
0 to 8V DC
[Input circuit]
Series
Thermistor
Specifications
TH
SC
10 kΩ
1 kΩ
8V DC
47

Related parts for 3G3JX-A2037