3G3JX-A2037 Omron Automation, 3G3JX-A2037 Datasheet - Page 37

no-image

3G3JX-A2037

Manufacturer Part Number
3G3JX-A2037
Description
Drive, Adjustable Frequency, 3-Phase, 240VAC, 5.0HP, 15.9A, RS-485 Serial , IP20
Manufacturer
Omron Automation
Type
Adjustable Frequencyr
Datasheet

Specifications of 3G3JX-A2037

Brand/series
JX
Current, Input
20 A
Function
Motor Control
Horse Power Rating
5 HP
Mounting Type
Screw
Phase
Three
Power Rating
5.0 HP
Primary Type
AC Drive
Standards
IP20
Voltage, Supply
240 VAC
Voltage, Supply Maximum
240
Lead Free Status / Rohs Status
RoHS Compliant part
■ Terminal Block Specifications
● Terminal Block Position
Control circuit terminal block
Note: This illustration shows the terminal block with the Terminal block front cover removed.
● Arrangement of Main Circuit Terminals
Terminal
P/+2, N/-
+1, P/+2
symbol
EMC filter functions switching method
Main circuit terminal block
Terminal arrangement
R/L1,
U/T1,
S/L2,
V/T2,
W/T3
P/+2,
T/L3
RB
G
R/L1
Ground terminal with
short-circuit bar (shaded area)
for EMC filter multi-function
switching
G
S/L2
Main power
supply input
terminal
Inverter output
terminal
External DC
reactor
connection
terminal
Braking resistor
connection
terminals
Regenerative
braking unit
connection
terminal
Ground terminal
Terminal name
Digital Operator
EMC filter enabled
T/L3
CHARGE LED indicator
+1
P/+2
Connect the input power supply.
Connect to the 3-phase motor.
Remove the short-circuit bar between terminals
"+1" and "P/+2", and connect the optional
power factor improvement reactor (DCL).
Connect optional external braking resistors.
(The RB terminal is provided for the Inverters
with 22 kW or lower capacity.)
Connect optional regenerative braking units.
Inverter case ground terminal. Connect this
terminal to the ground.
Class D (200 V), Class D (400 V)
When not using the DCL,
keep the +1-P/+2
short-circuit bar attached.
N/-
+1-P/+2 short-
circuit bar
RO TO
U/T1
V/T2
Description
EMC filter disabled (factory default)
RB
W/T3
G
Advanced General-purpose Inverters SYSDRIVE
●Emergency Shutoff Function
• The built-in slide switch is used to enable or disable the emer-
• This function is intended to turn off the Inverter output (Stop
gency shutoff function (Factory Default: Disabled).
switching the main element) via only the multi-function input
terminal of the hardware circuit, independent of the CPU Soft-
ware.
Slide lever (factory default: OFF)
Slide switch SW1
OFF
ON
RX
Series
45