INT-1532-L-5-L-010 TE Connectivity, INT-1532-L-5-L-010 Datasheet - Page 28

DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V

INT-1532-L-5-L-010

Manufacturer Part Number
INT-1532-L-5-L-010
Description
DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V
Manufacturer
TE Connectivity
Datasheet

Specifications of INT-1532-L-5-L-010

No. Of Digits / Alpha
4
Meter Function
Digital
Meter Range
0mA To 20mA
Digit Height
96mm
Supply Voltage Range
57.7V To 139V / 100V To 240V
Power Consumption
3W
Rohs Compliant
NA
ANSI Integra 1000 Series
Programmable Parameters
Multi-function Integra 1000 digital metering systems accurately
measure, display, and communicate electrical and power parameters
required for most power monitoring applications, including true rms
measurement of distorted waveforms.
This panel mounted enclosure offers simple programming and display of
up to 23 power measurement parameters via a menu driven user
interface on the front panel. Integra 1000 offers additional pulsed and
digital communication options, allowing remote monitoring of status
information via building management systems.
Operation
A two-button interface on the front panel of Integra 1000 units enables the simple
programming of VT and CT ratio settings, configuration of selected communication
options, and adjustment of operating parameters. To prevent unauthorised access
to the configuration settings, all screens offer password protection.
Once configured, status information can be viewed by scrolling through 11 screens
featuring a high contrast 3-line, 4-digit LED display, with separate annunicators for each
of the 23 measured parameters.
System Input
Designed for all low, medium and high voltage switchgear and distribution systems,
the Integra 1000 offers programmable VT and CT ratio capability. Direct connection of
up to 600V ac with 5A CT inputs is standard, and 1A CT inputs available as an option.
Pulsed Outputs
Integra 1000 offers an optional pulse output module enabling the retransmission of time-
based parameters. The output pulses at a rate proportional to the measured kWh active
energy, with pulse width and rate easily programmable via the set-up screens. The output
relay has a fully isolated volt free contact, with connection via screw-clamp terminals.
Digital Communications
RS485 Modbus RTU
Integra 1000 digital metering systems offer an RS485 communication port for direct
connection to SCADA systems using the Modbus RTU protocol, or the Johnson
Controls Metasys NII protocol. Remote monitoring enables the user to record the
systems parameters in real time, using high resolution numbers. The Modbus protocol
establishes the format for the master’s query by placing it into the device address. The
slave’s response is also constructed using the Modbus protocol; it contains the fields
confirming the action taken, the data to be returned, and an error-checking field. The
Modbus option includes the ability to change Modbus word order to suit the
requirements of the user.
Parameter
Password
Primary current
VT primary
Demand integration time
Reset
Pulse output duration
Pulse rate divisors
RS 485 interface baud rate
RS 485 parity
Modbus address
Range
4-digit 0000-9999
Max 9999:5 (360MW max**)
400kV (360MW max**)
** maximum VT or CT ratios are limited so
that the combination of primary voltage and
current do not exceed 360MW at 120% of
relevant input
8, 15, 20, 30 minutes
Max demand & active energy registers
60, 100, 200 milliseconds
1, 10, 100, 1000
2.4, 4.8, 9.6, 19.2 kB
Odd / even / no, 1 or 2 stop bits
1-247
Features
Measurement, display and
communication of up to 23 power
parameters
True rms measurement
Energy pulsed outputs
Digital communications
Fully programmable VT and
CT ratios
Simple menu driven interface
ANSI case style
High quality LED display
Benefits
Replaces multiple single function
instruments
Simple menu driven interface
Remote monitoring
Monitoring, control and protection
of power assests
Applications
Switchgear
Distribution systems
Generator sets
Control panels
Energy management
Building management
Utility power monitoring
Process control
Motor monitoring
Approvals
UL file no: 140758
IEC 1010 / BSEN 61010-1
27