EDS11-109E FUJI [Fuji Electric], EDS11-109E Datasheet

no-image

EDS11-109E

Manufacturer Part Number
EDS11-109E
Description
MICRO CONTROLLER "H"
Manufacturer
FUJI [Fuji Electric]
Datasheet
ler incorporating a micro processor, provides the digital
communication and high speed operation cycle (100 ms).
It is ideally suited for small scale plant or small scale FA
(Factory Automation).
FEATURES
1. Unique 2-size micro controller
2. High controllability
3. PID auto-tuning function
4. Dust/drip-proof front panel
5. Multi-input, programmable range
6. Full variety of operation and alarm functions
7. Full variety of control types
8. Wide range of power supply
DATA SHEET
Micro Controller “H”, Fuji's upgraded Z-series control-
(48 96mm, 96 96mm)
RS-485 digital communication has been realized with
these 3-size controllers.
High speed operation cycle (100 ms) his been attained.
PID parameters can be automatically computed and set
by the controller.
Front panel of dust/drip-proof construction conforms to
IEC IP55 standards.
Several inputs can be handled by a single controller.
Various operations and alarms are possible due do the
multiple input/output functions.
Inverter control type, position feedback control type and
dual control type are available for selection according
to final control devices.
The controller operates on power sources within the
range of AC 85 to 265V.
MICRO CONTROLLER H”
SPECIFICATIONS
1. Control operation functions
(1) PID control: Proportional band (P): 0 to 3276% (ON-
(2) PID auto-turning
(3) Operation cycle:
(4) Input filter:
(5) Square-root extraction (router):
(6) Input shift function:
(7) Intermittent PID control:
(8) Non-linear gain:
PYH5
Integral time (I): 0.1 to 3276 sec
Derivative time (D): 0 to 900sec
100 msec (operation cycle is variable
Setting range: 10.0 to 900.0 sec (set to
In differential pressure conversion, the
flow rate is treated as “0” by the router
cut point. (CUT point is “unused” prior to
delivery.)
Shift of actual measured value (PV) is
possible by this function.
Control cycle and control with/without
cycle can be designed without changing
100 msec (normal) of operation cycle.
A function to make a gain non-linearity
by reducing the gain in the vicinity of set
value (SV).
OFF operation of controller with dead
band at P=0)
within the range of 0.1 to 3276 sec)
10.0 sec prior to delivery)
PYH9
Date
EDS11-109e
P Y H
Oct. 28, 2003

Related parts for EDS11-109E

EDS11-109E Summary of contents

Page 1

... Shift of actual measured value (PV) is possible by this function. Control cycle and control with/without cycle can be designed without changing 100 msec (normal) of operation cycle. A function to make a gain non-linearity by reducing the gain in the vicinity of set value (SV). EDS11-109e Date Oct. 28, 2003 ...

Page 2

Table of input/output specifications and alarm output Item Input (measured value) Thermocouple, resistance bulb, voltage, current ................................................................................................................................................................................... With transmitter power supply 20mA (PYH9 only) mV input: leak current Control Relay contact ...

Page 3

Operating and storage conditions (1) Allowable ambient temperature: – (2) Allowable ambient humidity: 90 less (no condensation) (3) Storage temperature: – 10. General specifications (1) Power supply ...

Page 4

OUTLINE DIAGRAM (Unit:mm) PYH9 (96 96mm) 96 FLT SV/MV A/M SEL DATA Panel cutout Note 3) Note 3) 30 Min.100 30 +0 PYH5 (48 96mm) 48 ...

Page 5

CONNECTION DIAGRAM PYH9 With transmitter + Power supply 1 TRX1 Digital + communication 5 2 TRX2 RS485 Shield 3 SHLD + 6 4 PV1 A Input signal (PV) 5 PV2 B 6 PV3 B 7 SC/ (min) 8 CAS + ...

Page 6

PYH Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 ...

Related keywords