Responding to Displayed Error Messages
236
[No Starting Screen]
Specified Starting Screen is not saved.
Fix Screen Data using by the Support
Tool.
Then set the PT to the TRANSMIT
MODE and download Screen Data again.
[Touch Panel is disconnected]
[Memory Switch Corrupted]
Because Memory Switch setting was
last. Initialized Memory Switch setting.
Press Confirm to return to the SYSTEM
MENU.
[Calendar Data Error]
Calendar Data is incorrect.
Set to the MAINTENANCE MODE and
set Calendar Data.
[Backup Data Error]
Memory table and History data was ini-
tialized by backup failure.
It can be caused by lowered voltage of
the battery.
[With memory switch setting screen]
Invalid Comm. Method
Message
No data is registered for either the
screen number set in the PT sta-
tus control area or the Initial
Screen set with the Support Tool.
Or the screen number which does
not exist are registered.
The touch panel cable (film cable)
inside the NT31/NT31C is discon-
nected.
The memory switches have been
initialized due to discovery of an
error in the memory switch set-
tings.
There is an error in the date/time
values due, for example, to low
battery voltage.
Initialization has been executed
because of an error in the backup
data area.
Protocol settings for serial port A
and serial port B are mismatched.
Cause
Either specify a screen number for which
data is registered at the PT status control
area, or set the screen as the Initial
Screen in the System settings under PT
Configuration at the Support Tool.
Contact your OMRON service center.
Set the memory switches again using the
System Menu and the System settings
under PT Configuration at the Support
Tool. (SECTION 6 System Menu Opera-
tion)
If the problem recurs, contact your
OMRON service center.
Check the battery voltage by checking the
color of the RUN LED and with the battery
check in the System Menu; if the voltage is
low, replace the battery with a new one.
(Checking the Battery Voltage, page 213,
and 7-3-1 Replacing the Battery,
page 243)
If the battery voltage is confirmed to be
normal, set the calendar clock correctly
from the System Menu. (6-11-2 Display-
ing/Setting the Calendar and Clock,
page 195)
Check the battery voltage by checking the
color of the RUN LED and with the battery
check in the System Menu; if the voltage is
low, replace the battery with a new one.
(Checking the Battery Voltage, page 213,
and 7-3-1 Replacing the Battery,
page 243) The re-transmit the memory
table data from the Support Tool.
If the voltage is normal and the problem
recurs, contact your OMRON service cen-
ter.
Refer to Possible Combinations of Com-
munications Method Settings on page 160
and set the protocol of serial port A and
serial port B so that their settings are
matched.
* Set serial port A to “None” when con-
necting the Support Tool and the host at
the same time.
Remedy
Section 7-2