DCN4-BR4D Omron, DCN4-BR4D Datasheet - Page 106

no-image

DCN4-BR4D

Manufacturer Part Number
DCN4-BR4D
Description
Thin Cable-Flat Cable Conv Con
Manufacturer
Omron
Datasheet

Specifications of DCN4-BR4D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
2-6
Operational Checklist
Network configura-
tion and wiring
Devices supplied by
communications
power supply
Category
Operational Checklist
Connectors
Terminators
Max. network
length
Branch line
length
Cables
Shield wire
ground
Other
Power supply
capacity
Isolation
Item
Are the connectors and cables to the Master connected cor-
rectly? (Do the wire colors match the colors next to the Mas-
ter’s DeviceNet connector?)
Are the connectors and cables to the Slaves connected cor-
rectly? (Do the wire colors match the colors next to the Slaves’
DeviceNet connectors?)
Are the connectors securely connected?
Is there a possibility that the cable connectors will be pulled
out because of the cable weight?
If the connectors have attachment screws or mounting brack-
ets, are the screws/brackets tightened properly?
Have Terminating Resistors been connected at both ends of
the trunk line?
Are the specified Terminating Resistors being used?
If a T-branch Tap is being terminated, is the Terminating
Resistor seated properly in the T-branch Tap’s socket?
Is the length of the network within specifications?
Are all branch lines 6 m or shorter?
Is the total branch line length within specifications?
Can the cable supply the current required by all of the nodes
that are connected?
Is the proper DeviceNet cable being used?
Are the cables separated from any power or high-voltage
lines?
Have the cables been handled carefully, without excessive
force?
Is the network be grounded in only one location?
Is a separate ground line used? (Is the ground line separated
from any power line ground?)
Are there any devices in the network that are not DeviceNet
products?
Has the power supply requirement been calculated using
each node's current consumption?
Can the power supply handle the inrush current when the sys-
tem is started?
Is the DC output isolated from the AC input in the power sup-
ply?
Check
Section 2-6
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Result
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
85