BA9026 ETC, BA9026 Datasheet

no-image

BA9026

Manufacturer Part Number
BA9026
Description
Power Electronics, Softstarter with Softstop Ministart
Manufacturer
ETC
Datasheet
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
Block diagram
Power Electronics
Softstarter with softstop BA 9026
ministart
Function diagram
T1 / T2 / T3
L1 / L2 / L3
X1 / X2
A1 / A2
M Mot
n
t 0 -t 1
t 2 -t 3
t 0
t
0
:
:
:
start
ramp up time
ramp down time
t
1
t
2
t
3
M7038_a
t
Softstarts are electronic devices designed to enable 1-phase or 3-phase
induction motors to start smoothly. The BA 9026 slowly ramps up the
current on three phases, therefore allowing the motor torque to build up
slowly. This reduces the mechanical stress or the machine and prevents
damage to conveyed material.
When the motor is up to full speed the semiconductors in BA 9026 are
bridged to prevent internal power losses and heat build up to addition
BA 9026 allows a softstop function prolonging the stop time of the motor
preventing high counter torques from abruptly stopping the motor.
LED green
LED yellow
LED red
For direct on line or star delta applications, terminals L1, L2, L3 are
connected to the mains contactor, with the motor connected to terminals
T1, T2, T3. A 24 V DC auxiliary supply is connected to terminals A1, A2
and a 24 V DC control signal connected to terminals X1-X2.
When power is connected to terminals L1, L2, L3 and 24 V DC is present
at terminals X1-X2, the softstart will commence. Potentiometer
"t
and potentiometer "M
the softstart is complete the internal semiconductors are automatically
bridged.
When 24 V DC is removed from terminals X1-X2, the softstop function will
commence for the deceleration time period set on potentiometer
"t
"M
Motor load must always be connected as continuous operation of the
softstart with no load may cause overheating of the motor and softstart.
It is recomended that the softstart is protected by superfast semiconductor
fuses rated as per the current rating of the softstart of motor. However,
standard line and motor protection is acceptable, but for high starting
frequencies motor winding temperature monitoring is recommended.
1
an
ab
Approvals and marking
Applications
Function
Indication
Principle of operation
Notes
Increases the life of squirrel cage motors and mechanical drives
Easily fitted to existing installations
3-phase control softstart and softstop
For motors up to 3 kW
Start current limited to 2 to 3 times rated motor current
Semiconductors bridged after softstart
Adjustable ramp time, starting torque and deceleration time
LED indication
DIN rail mounted
Galvanic isolation of control input and auxiliary power supply
Integrated overtemperature monitoring
Wide motor voltage range 200 to 460 V AC
Width 45 mm
Motor with gear, belt or chain drive
Fans, pumps, conveyor systems, compressors
Packaging machines, door-drives
Start current limiting on 3-phase motors
Reduces on off current on transformers and P.S.U's
ab
" (0,5-5s) adjustst the ramp time (time motor takes to get to full speed)
" (0,5-5s) and deceleration voltage level set on potentiometer
" (30-80 % nomV).
ON
ON
ON
an
" adjusts the start voltage (50-80 % nomV). When
=
=
=
power connected
power semiconductors bridged
overtemperature
BA 9026 / 12.11.02 d

Related parts for BA9026

BA9026 Summary of contents

Page 1

Power Electronics Softstarter with softstop BA 9026 ministart Function diagram Mot start ...

Page 2

... Please note, that even if the motor is at rest not physically separated from the mains. Because of this the motor must be disconnected from the mains via the corresponding manual motor starter. S1 I> I> I> (+) (+) BA9026 M6436_a M 3 ...

Related keywords