EDS11-160C FUJI [Fuji Electric], EDS11-160C Datasheet

no-image

EDS11-160C

Manufacturer Part Number
EDS11-160C
Description
Manufacturer
FUJI [Fuji Electric]
Datasheet
PX series
digital temperature
controller
PXG9 is a compact size temperature controller of front panel
size 96
temperature controller, it has many input/output points and
sophisticated control functions.
FEATURES
1. Wide variety and number of input / output
2. User interface of easy-to-see indication and easy-to-use
3. Advanced control functions to meet various applications
4. A variety of functions extending the possibility of tem-
DATA SHEET
1. Digital input: Up to 5 points
2. Digital output: Up to 5 points
3. Control output: 4 types
4. Universal inputs: Thermocouple, resistance bulb, cur-
5. Remote SV input function
6. Analog re-transmission output function (for current or
7. Motorized valve control output
1. Easy-to-see, large display section
2. Parameters grouped by functions
3. User key to which you can assign a function
4. Password function provided for avoiding wrong opera-
5. Front water-proof structure (IP66 in corformity)
1. Sampling cycle 200 ms (300 ms at position feedback
2. Input indication accuracy
3. Manual control function
4. Control method selectable out of 8 different types:
5. Heating/cooling control selectable
6. Auto tuning function
1. Guarantee soak function provided, 16 step ramp/soak
2. 8 PID setting pallets, 8 SV pallets capable of frequent
3. Soft start function that limits MV output when start-
4. Ramp SV function enables graduate change of SV
5. Loop burnout alarm, heater burnout alarm and differ-
6. Control standby function
7. Loader interface (RS232C)
8. RS485 communication (option)
operation method
perature controller
Relay contact, SSR drive, voltage linear, current linear
rent, voltage, mV linear
voltage)
tion and protecting settings
cotrol)
ON/OFF control, PID control, fuzzy PID control, self-
tuning control, PID2 control, motorized valve control
(with/without position feedback)
function
change of control
ing up
ent event outputs are available in digital output (op-
tion)
96 mm. To cope with any of versatile uses as a
0.3%FS
MICRO-CONTROLLER X (96 96 mm)
SPECIFICATIONS
(1) Power supply :
(2) Power consumption:
(3) Insulation resistance:
(4) Withstand voltage:
(5) Approvals and certification:
1. General Specifications
100 V ( - 15%) to 240 V (+ 10%) AC,
50/60 Hz
24 V ( 10%) DC. 24 V ( 10%) AC,
50/60 Hz.
12 VA MAX.
20 M
Power source
Relay contact output
Between others
UL(UL873), C-UL(CSA C22.2 No.24-93 or
equivalent), CE mark(LVD : EN61010-1,
EMC : EN61326-1)
MIN. (at 500 V DC)
all terminals
1500 V AC for 1 min
1500 V AC for 1 min
500 V AC for 1 min
all terminals
Date
EDS11-160c
PXG9
Apr. 1, 2011

Related parts for EDS11-160C

EDS11-160C Summary of contents

Page 1

... Withstand voltage: Power source all terminals 1500 V AC for 1 min Relay contact output 1500 V AC for 1 min Between others 500 V AC for 1 min (5) Approvals and certification: UL(UL873), C-UL(CSA C22.2 No.24-93 or equivalent), CE mark(LVD : EN61010-1, EMC : EN61326-1) PXG9 all terminals EDS11-160c Date Apr. 1, 2011 ...

Page 2

PXG9 2. Input section 2.1 Process value input (1) Number of inputs: 1 point (2) Input setting: Programmable scale (3) Input signal: See Table 1 (thermocouple, resistance bulb, mV, voltage, current(With external 250 resistance) universal input) (4) Standard measurement range ...

Page 3

Output section 3.1 Control output (1) Number of points points (2 points: Heating/cooling control) (2) Type: selected out of [1] to [5] below [1] Relay contact output • Proportional cycle 150 sec • Contact ...

Page 4

PXG9 4. Indication/setting section 4.1 Display unit (1) Type: LED (2) Indication contents: Process value indication: 7 segments, 4 digits [red] Setpoint indication: 7 segments, 4 digits [green] Indication status: 6 indicator lamps 4.2 Setting section (1) Type: Sheet type ...

Page 5

Structure (1) Mounting method: Mounted with panel (2) External terminals: Screw terminals, M3 (3) Case: • Material: ABS, and degeneration PPO • Non-combustibility grade: UL94V-0 equivalent • Color: Black (4) Protection structure: • Panel front side: IP66, NEMA-4X equiva- ...

Page 6

PXG9 CODE SYMBOLS Standard type Digit Specifications 4 <Front panel size W H> 96 96mm 5 <Output 1> Relay contact SSR drive Current ( DC DC) Voltage ( DC ...

Page 7

CODE SYMBOLS Motorized valve control type Digit Specifications 4 <Front panel size W H> 96 96mm 5 <Output 1> Motorized valve control output (Without PFB) Motorized valve control output (With PFB) 6 <Output 2> None Auxiliary Digital output Transmitter power ...

Page 8

PXG9 OPTIONALLY ITEMS Instruction manual for communication functionRS485 (Modbus) Current detector for heater burnout alarm Rear terminal cover Shunt resistor 250 0.1% PC loader communication cable TABLE 1 [1] Unit of temperature: ˚C Input Input type code 0 JPt100 Resistance ...

Page 9

OUTLINE DIAGRAM (Unit : mm) 96 Water-proof packing 37-48 49-60 61-72 1-12 13- Rear view Mounting bracket 94.5 (terminal cover included Panel PC loader ...

Page 10

PXG9 OPTIONALLY ARRANGED ARTICLES Heater current detector (CT) . Specification : Type : CTL-6-S 5 Note 1) Detection is available only for single phase heater. Note 2) Unusable for heater control ...

Page 11

EXTERNAL CONNECTION DIAGRAM Standard type with communication OPTION1 RS485,DI1,RSV1,CT1 RS485+DI+RSV1 RS485+RSV1/RS485+CT1/RS485+ RS485 RS485 RS485 2 2 DI1 3 3 RSV1 CT1 4 DI-COM 4 5 RSV1 6 TOP TOP ...

Page 12

PXG9 Standard type without communication OPTION 1 DI1,DI2,RSV1,CT1 DI1+DI2+RSV1 DI1+RSV1/DI1+CT1/DI1+DI2 DI1 1 1 DI1 DI- DI-COM 2 2 COM DI2 3 3 RSV1 RSV1 6 TOP TOP PS Power supply DO DO1- COM DO1 11 11 DO2- ...

Page 13

Motorized valve control type with communication OPTION 1 RS485,DI1,DI2,DI3,RSV1 RS485+DI+RSV1 RS485+DI1+DI2+DI3 1 RS485 RS485 2 DI1 DI1 3 DI-COM 4 DI-COM DI2 5 RSV1 6 DI3 TOP TOP PS Power supply DO DO1- COM DO1 11 11 DO2 ...

Page 14

PXG9 Motorized valve control type without communication OPTION 1 DI1,DI2,DI3,RSV1 DI1+DI2+DI3+RSV1 DI1 DI- COM DI2 DI3 RSV1 TOP TOP PS Power supply DO DO1- COM DO1 11 11 DO2 COM DO2 100-240VAC 24VAC/24VDC 50/60Hz 50/60Hz ...

Page 15

ISOLATED BLOCK DIAGRAM Power supply Control output 1 (relay contact) or OPEN output Control output 2 (relay contact) or CLOSE output Digital output 1 (relay contact) Digital output 2 (relay contact) When the 9th digit of the code symbols = ...

Page 16

PXG9 ...