Manufacturer Part Number
EDS11-160C
Description
Manufacturer
FUJI [Fuji Electric]
Datasheet
4
4.1 Display unit
(1) Type:
(2) Indication contents:
4.2 Setting section
(1) Type:
(2) Number of keys: 4 keys.
5.1 Control types
(1) 2-position control (set parameter P to 0%)
(2) PID control (fuzzy PID included)
(3) PID dual (heating, cooling) function (fuzzy PID included)
(4) Motorized valve control (position feedback or servo
5.2 Control parameters
• Proportional band (P):
• Integral time (I): 0 to 3200 sec. Integral time control in-
• Differential time (D):
• Control cycle:
• Anti-reset windup:
• Hysteresis band:
• Number of SV and PID combinations:
5.3 Control mode
(1) Mode type:
(2) Mode changeover:
4. Indication/setting section
5. Control functions
PXG9
control)
• PID parameters determination: Auto tuning,
Process value indication: 7 segments,
4 digits [red]
Setpoint indication: 7 segments, 4 digits
[green]
Indication status: 6 indicator lamps
• PID parameters determination: Auto tuning
• Full stroke time: 30 sec MIN.
0.0 to 999.9%. 2-position control when
P = 0.
validated when I = 0.
0.0 to 999.9 sec. Differential time con-
trol invalidated when D = 0.
control)
0 to 100% of measurement range
50% of measurement range (at 2-posi-
tion control only)
Changed by any of parameter setting,
digital input, communication and user
function keying
* In case of 2 position control in manual
Auto
A u t o / M a n u a l
bumpless
A u t o / M a n u a l
bumpless
LED
Sheet type keys (with emboss)
200 ms (300 ms at position feedback
8 combinations.
Auto, Manual, Remote
key
SEL ,
mode, 2 positions correspond to
MV = 100 or 0%.
selftuning
Manual: Balanceless · bumpless
,
R e m o t e : B a l a n c e ·
R e m o t e : B a l a n c e ·
plus user function
6.1 Number of alarm setting points
• Up to 5 points (depends on number of DO)
6.2 Alarm type
• Process value (upper limit/lower limit, absolute/devia-
6.3 Heater burnout alarm function
(1) Detectable range:
(2) Detected current resolution:
(3) Setting resolution:
(4) Hysteresis:
7.1 RS-485 interface
(1) Number of points: 1 point
(2) Physical specifications: EIA RS485
(3) Protocol:
(4) Communication method:
(5) Code type:
(6) Communication rate:
(7) Connection status:
(8) Communication distance:
• Memory protection:
• Method:
(1) Operating ambient temperature:
(2) Storage temperature:
(3) Operating/storage ambient humidity:
(4) Warm-up time:
(5) Vibration:
(6) Impact:
6. Alarm function
tion, range), main unit error, etc.
(non-excitation, delay, latch, timer function option provided)
7. Communication function
8. Processing at power failure
9. Self-diagnosis
10. Operation and storage conditions
Half duplex bit serial, Asynchronous com-
munication
none.
9600 bps, 19200 bps
Up to 32 units connectable including multi-
drop master function
Up to 500 m (total connect extension)
Protect by non-volatile memory
timer
-20 to 60˚C
90%RH MAX. (no condensing)
30 min MIN
1 to 50 A
0.1 A
0.1 A
0.0 to 50.0 A
Modbus-RTU
Data length 8 data bits. Parity Odd, even,
Program error supervision by watchdog
10 to 70 Hz, 9.8 m/s
49 m/s
-10 to 50˚C
2
(5 G) MAX.
2
(1 G) MAX.