2726188 Phoenix Contact, 2726188 Datasheet - Page 143

no-image

2726188

Manufacturer Part Number
2726188
Description
INTERBUS Bus Coupler
Manufacturer
Phoenix Contact
Datasheet
11 Inline Modular IO: Technical data and ordering data
6452_en_02
System data
Number of devices in an Inline station
Maximum current consumption of the Inline terminals
General data
Instructions
Ambient temperature
Temperature cycles
(Speed of changing from positive to negative temperatures and vice versa)
Permissible humidity (operation/storage/transport)
Permissible air pressure (operation/storage/transport)
Degree of protection
Class of protection
Air and creepage distances
Housing material
Ambient temperatures (operation)
Ambient temperature (storage/transport)
When configuring an Inline station, observe the power supply through the bus couplers, power terminals, and segment terminals, as well as
the current consumption of each device. This information is provided in the DB GB IB IL DEVICE LIST data sheet and in the relevant terminal-
specific data sheet. It can differ depending on the individual terminal. If the maximum current carrying capacity of a potential jumper is
reached, a new power terminal must be used or a new station must be created.
This table provides standard data. For different values, please refer to the terminal-specific data sheets.
The technical data does not claim to be complete. Technical modifications reserved.
11.1
For the system data for your bus system, please refer to the corresponding
documentation.
If you are using Inline in a system with other product ranges, also observe the technical
data for these product ranges. Please refer to the corresponding documentation for this
technical data.
The following values are standard values for the preferred mounting position (horizontal
DIN rail). For different values, please refer to the terminal-specific data sheets.
Technical data for Inline Modular IO
63 devices, maximum; see documentation for bus couplers
See terminal-specific data sheet or DB GB IB IL DEVICE LIST data sheet
Developed according to EN 50178/IEC 62103, UL 508
-25°C … +55°C
-25°C … +85°C
0.5 K/min (no condensation)
10% ... 95%, according to DIN EN 61131-2
70 kPa ... 106 kPa (up to 3000 m above sea level)
IP20
III, IEC 61140
According to IEC 60644/IEC 60664A, DIN VDE 0110 and
EN 50178/IEC 62103, DIN VDE 0160
Plastic, PVC-free, PA6.6, self-extinguishing (V0)
Inline Modular IO: Technical data and ordering data
PHOENIX CONTACT
11-1