2726188 Phoenix Contact, 2726188 Datasheet - Page 37

no-image

2726188

Manufacturer Part Number
2726188
Description
INTERBUS Bus Coupler
Manufacturer
Phoenix Contact
Datasheet
Features
Connections
Carrying capacity of the
jumper contacts
Protective earth
grounding (PE)
Voltage area
Additional documentation
6452_en_02
4.2.6
Figure 4-9
Different power-level terminals are available for direct switching, protection, and monitoring
of three-phase standard motors via a bus system:
Connections for the mains supply input, remote cabling, motor output, hand-held operator
panel mode, and a brake are available on a power-level terminal.
The maximum current carrying capacity of the jumper contacts on the side is specified in
"Current and voltage distribution" on page 7-12.
The power-level terminal is connected to protective earth ground via the mains connection.
Power-level terminals must be installed in a 24 V DC area within an Inline station. Operation
in a different voltage area is not permitted.
For more detailed information about the function, properties, wiring, and parameterization
of the individual terminals, please refer to the terminal-specific documentation.
Power-level terminal as electronic direct starter
for motors up to 1.5 kW/400 V AC
Power-level terminal as electromechanical direct starter
for motors up to 3.7 kW/400 V AC
Power-level terminal as electronic reversing load starter
for motors up to 1.5 kW/400 V AC
Electronic motor protection
Motor current parameterization via a bus system
Motor current monitoring
Quick shutdown
Mains voltage up to 400 V AC or 520 V AC, maximum (without tolerance in
electromechanical versions)
Nominal output power of 1.5 kW to 3.7 kW depending on the version
Hand-held operator panel mode
Can be extended with brake function as an option
Thermal motor monitoring using connected thermistor terminal
Power-level terminals
Power-level terminal
PHOENIX CONTACT
Inline product groups
4-13

Related parts for 2726188