2726188 Phoenix Contact, 2726188 Datasheet - Page 26

no-image

2726188

Manufacturer Part Number
2726188
Description
INTERBUS Bus Coupler
Manufacturer
Phoenix Contact
Datasheet
IL SYS INST UM E
Scope of supply
Local bus transmission
speed
Examples
Convention for this
document
4-2
IB IL 24 DI 2-PAC
IB IL 24 DI 2-2MBD-PAC
IB IL 24 DI 2
PHOENIX CONTACT
4.2
4.2.1
Inline terminals are predominantly available as complete items. This is indicated in the order
designation by the extension "-PAC". The following are supplied as standard with a
complete item:
In the past, Inline terminals were available as stand-alone items without accessories. For a
stand-alone item without accessories, the Inline connectors and labeling fields have to be
ordered separately.
It is possible to operate at a transmission speed of 500 kbps or 2 Mbps within an Inline
station.
Items designed for 2 Mbps are indicated by the extension "-2MBD" in the order designation.
The versions without this extension are designed for 500 kbps.
For INTERBUS, a separate bus coupler version is available for each transmission speed.
Bus couplers for other bus systems may only support terminals with 500 kbps or even both
transmission speeds in the local bus.
Examples of order designations:
The PAC version for 500 kbps is used in the following examples. However, all information
also applies for the versions for 2 Mbps and the versions without accessories.
500 kbps; complete with accessories (connectors and labeling fields)
2 Mbps; complete with accessories (connectors and labeling fields)
500 kbps; without accessories
In the product range, terminals with 500 kbps are basic versions. Some (not all) of the
terminals are also available as 2MBD versions. Additional information about the available
terminals can be found in the latest "AUTOMATION" catalog or on the Internet at
www.phoenixcontact.com.
NOTE:
Use the same transmission speed throughout an Inline station. The station cannot
operate otherwise. Make sure that your bus coupler supports this transmission speed in
the local bus.
For details of which transmission speed your bus coupler can use within the local bus,
please refer to the corresponding documentation, the "AUTOMATION" catalog or
"AH IL BK IO LIST".
The electronics base
All required Inline connectors
All required labeling fields
Inline Modular IO terminals
Scope of supply and transmission speed
6452_en_02