H8GN-AD DC24 Omron, H8GN-AD DC24 Datasheet - Page 16

no-image

H8GN-AD DC24

Manufacturer Part Number
H8GN-AD DC24
Description
TIMER/COUNTER 1/32DIN 24VDC
Manufacturer
Omron
Series
H8GNr
Datasheet

Specifications of H8GN-AD DC24

Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H8GN-ADDC24
H8GNADDC24
Communications Setting Level
The communications specifications are set in the communications
setting level. Make the individual communications settings from the
front panel.
The communications parameters and their settings are listed in the
following table.
Note: 1. The settings shown in reverse video are the default settings.
Before performing communications, perform the following procedure
with the front panel keys to set the communications unit number,
baud rate, and other settings. Refer to the communications manual
for operation methods for other communications settings.
Align each communications setting with the settings on the personal
computer or other communications device.
1. Communications Unit Number (u-no)
2. Baud Rate (bps)
3. Communications Data Length (len)
4. Stop Bits (sbit)
Communications
unit number
Baud rate
Communications
data length
Stop bits
Parity
1.Press the
2.Press the
3.Press the
4.Use the
When communicating with a host computer, set a unit number to
enable the host computer to identify each unit. The number can
be set in a range from 0 to 99 in increments of 1. The default unit
number is 1. When using multiple units, the units will not function
normally if the same unit number is set for more than one unit.
Set the baud rate for communications with the host computer. The
settings correspond to the following baud rates.
1.2 (1,200 bps), 2.4 (2,400 bps), 4.8 (4,800 bps), and 9.6
(9,600 bps).
The communications data length can be changed to either 7 or 8
bits.
The stop bits can be set to either 1 or 2.
Parameter
2. Settings made in the communications setting level are en-
operation level to the initial setting level.
communications setting level.
below.
abled when the power is turned ON again.
and
u-no
bps
len
sbit
prty
Key and move from the initial setting level to the
Display
Key for at least 3 seconds and move from the
Key to change the settings items as shown
(1) Communications unit number
(2) Baud rate
(3) Communications data length
(4) Stop bits
(5) Parity
Keys to change the settings data.
0 to 99
1.2, 2.4,
4.8, or 9.6
(kbps)
7/8 (bits)
1/2
None,
even, or
odd
Settings
0 /
1.2 / 2.4 / 4.8 /
7
1 /
none /
odd
/ 8
1
2
to
Set value
euen
99
/
9.6
5. Parity (prty)
The parity can be set to none, even, or odd.
H8GN
16

Related parts for H8GN-AD DC24