H8GN-AD DC24 Omron, H8GN-AD DC24 Datasheet - Page 7

no-image

H8GN-AD DC24

Manufacturer Part Number
H8GN-AD DC24
Description
TIMER/COUNTER 1/32DIN 24VDC
Manufacturer
Omron
Series
H8GNr
Datasheet

Specifications of H8GN-AD DC24

Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H8GN-ADDC24
H8GNADDC24
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Safety Precautions
Refer to Safety Precautions for All Counters.
Tighten the terminal screws to the specified torque (approx. 0.5 N⋅m).
Fire or malfunction may result if the screws become loose.
Do not use the product in locations subject to flammable or explosive
gases. Doing so may result in explosion.
The service life of the output relays depends on the switching capacity
and switching conditions. Consider the actual application conditions
and use the product within the rated load and electrical service life.
Using the product beyond its service life may result in contact
deposition or burning.
Do not disassemble, repair, or modify the product. Doing so may
result in electric shock, fire, or malfunction.
Do not allow metal objects or conductive wires to enter the product.
Doing so may result in electric shock, fire, or malfunction.
Other Precautions
• Store at the specified temperature. If the H8GN has been stored at
• Use the product within the ratings specified for vibration, shock,
• Do not use the product in locations subject to dust, corrosive
• Use the product within the ratings specified for temperature and
• The product is designed for 24 VDC. Applying voltages other than
• Separate the input signal devices, input signal cables, and the
• Separate the product from the source of static electricity when
• Do not expose the product to organic solvent such as thinner or
H8GN
a temperature of less than −10°C, allow the H8GN to stand at room
temperature for at least 3 hours before use.
submerging in water, and exposure to oil.
gases, or direct sunlight.
humidity.
the rated one such as 100 to 240 VAC may damage the internal
elements.
product from the source of noise or high-tension cables producing
noise.
using the product in an environment where a large amount of static
electricity is produced (e.g., forming compounds, powders, or fluid
materials being transported by pipe).
benzine, strong alkali materials, or strong acid materials. Doing so
may damage the product surface.
No. 1 display digit size
3.3 mm
7 mm
!CAUTION
No. 2 display digit size
1.6 mm
3.4 mm
M3 terminal screw
Application Precautions
1. Do not use the product in locations where condensation may
2. Be sure to wire terminals correctly, with the correct polarity.
3. Maintain the power supply voltage within the allowable ranges.
4. Connect the power supply through a relay or switch so that the
5. When the power is turned ON, an inrush current (approx. 15 A)
6. For the main power supply or the power supply for input devices,
7. Leaving the H8GN with outputs ON at a high temperature for a
occur due to high humidity or where temperature changes are
severe.
voltage reaches a fixed value immediately. If the voltage
increases gradually the power supply may be reset or outputs
may turn ON.
will flow momentarily. Depending on power supply capacities, the
product may not start due to this leakage current. The power sup-
ply must be of a sufficiently large capacity.
use a power supply transformer whose primary side is insulated
from the secondary side and whose secondary side is not
grounded.
long time may hasten the degradation of internal parts (such as
electrolytic capacitors). Therefore, use the product in combination
with relays and avoid leaving the product as long as more than 1
month with the output turned ON.
Separate
mounting
insert the adapter from the back, and
push the H8GN into the cutout as far
as possible. Use screws to secure the
H8GN. To make the H8GN waterproof,
insert waterproof packing and tighten
the screws.
in a cutout, be sure that the ambient
temperature does not exceed the
specifications.
Insert the H8GN in the square cutout,
When mounting two or more products
40 min.
Panel cutout
The product cannot
be made waterproof
when gang-mounted.
(48 × No. of units
− 2.5)
Gang mounting
+1.0
0
H8GN
7

Related parts for H8GN-AD DC24