C30CNE20A0 EATON CUTLER HAMMER, C30CNE20A0 Datasheet - Page 10

Lighting Contactor

C30CNE20A0

Manufacturer Part Number
C30CNE20A0
Description
Lighting Contactor
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of C30CNE20A0

No. Of Poles
2
Contact Configuration
DPST-NC
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
120V
Contact Current Max
30A
Mounting Type
DIN Rail
External Height
187.6mm
Continuous Load Current
30A
Operating Voltage
600VAC
Switching Current Ac1
30A
Switching Current Ac3
30A
Load Current Inductive
30A
Contactor Direction
Reversing
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
37
37-10
Components
Electrically Held Base
Contactor
The C30CNE20_0 Electrically
Held Base Contactor contains
a 2NO power pole as standard
and will allow the addition of
power poles to build an Elec-
trically Held Contactor up to
12 poles maximum. A
Mechanically Held Module Kit
can also be added to convert
the Electrically Held Contac-
tor into a Mechanically Held
Contactor in the field.
Table 37-20. Electrically Held Base Contactor
Table 37-21. Coil Base Voltage (Digit 8)
Power Poles
The C30CNM contactor accepts up to a maximum 6 single- or
double-pole (or combinations) power poles. These can be
used to form up to:
Table 37-22. Power Poles
Power Poles
2NO
Voltage
(Digit 8)
115 – 120V 60 Hz/110V 50 Hz
230 – 240V 60 Hz/220V 50 Hz
460 – 480V 60 Hz/440V 50 Hz
575 – 600V 60 Hz/550V 50 Hz
200 – 208V 60 Hz
265 – 277V 60 Hz/240V 50 Hz
24V 60 Hz/20V 50 Hz
28V 60 Hz/24V 50 Hz
347V 60 Hz
Power Poles
Single-Pole
Double-Pole
When ordering, select required contactor by Catalog Number and
replace the magnet coil alpha designation in the Catalog Number (_)
with the proper Code Suffix from Table 37-21.
12 NO poles max. when 6 double-poles are used in NO
positions (1 – 6) or
8 NC poles max. with 4 double-poles in the NC position
(1 – 4) and 4 NO poles with 2 double-poles in the 2 NO
positions (5 – 6)
Lighting Contactors
Open Control
C30CN Mechanically Held
Catalog Number
C30CNE20_0
Power Poles
Catalog
Number
C320PRP1
C320PRP2
Electrically Held
Base Contactor
Price
U.S. $
Price
U.S. $
For more information visit: www.eaton.com
Code
Suffix
A
B
C
D
E
H
T
V
X
Mechanically
Held Module Kits
These kits are for
converting
electrically held
contactors to
mechanically held
units. Kits include
control module,
latch, latch cover
and auxiliary
contacts plus installation instructions. Conversion kits are
suitable for coil voltages of 277V and below.
Table 37-23. Mechanically Held Module Kits
2-Wire
3-Wire
Figure 37-4. C30CNM Components — Exploded View
Coil Volts
24 – 277V AC
24 – 277V AC
Control Volts
110 – 120V AC
200 – 277V AC
24V AC
12 – 24V DC
110 – 120V AC
200 – 277V AC
24V AC
12 – 24V DC
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-1C
Catalog
Number
C320MH2WA0
C320MH2WH0
C320MH2WT0
C320MH2WT1
C320MH3WA0
C320MH3WH0
C320MH3WT0
C320MH3WT1
Conversion Kits
CA08102001E
Price
U.S. $
June 2008

Related parts for C30CNE20A0