C30CNE20A0 EATON CUTLER HAMMER, C30CNE20A0 Datasheet - Page 9

Lighting Contactor

C30CNE20A0

Manufacturer Part Number
C30CNE20A0
Description
Lighting Contactor
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of C30CNE20A0

No. Of Poles
2
Contact Configuration
DPST-NC
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
120V
Contact Current Max
30A
Mounting Type
DIN Rail
External Height
187.6mm
Continuous Load Current
30A
Operating Voltage
600VAC
Switching Current Ac1
30A
Switching Current Ac3
30A
Load Current Inductive
30A
Contactor Direction
Reversing
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
June 2008
Operation
3-wire control is the choice for use
with momentary devices allowing
operation from multiple locations. A
momentary pulse of energy operates
the contactor while a second pulse on
an alternate leg returns the contactor
to its original state.
2-wire control is the choice for single
output automatic operation or for
operation from single-pole devices.
When voltage is applied to the input
terminals the contactor is latched into
position (coil is removed from the cir-
cuit while control voltage is continu-
ously supplied). When control voltage
is removed, the latch is disengaged
and the contactor is returned to its
original state.
Instructional Leaflets
50765
50766
50767
50768
Standards and Certifications
CA08102001E
UL Listed File E1491, UL Category
Code/Guide NLDX/NLDX7
cUL
CE
C30CN Lighting
Contactor Series
Coil Kit for C30CN
Lighting Contactors
Power Pole Kit for C30CN
Lighting Contactors
Control Module Kit for
C30CN Lighting Contactors
Technical Data and Specifications
Main Power Poles
Table 37-14. Maximum AC Voltage and Amp
Ratings
Table 37-15. Maximum Horsepower Rating
1 Pole, Single-Phase
3 Poles, Three-Phase
Wire Size
Table 37-19. Wire Specifications
Load Type
Ballast
General Use 30
Tungsten
AC Resistive 30
Normal Starting Duty
Volts
110 – 120V
220 – 240V
Volts
200 – 208V
220 – 240V
440 – 480V
550 – 600V
Component
Power Poles
Coil
Control Module
Auxiliary Contacts
For more information visit: www.eaton.com
8 AWG stranded only.
Lighting Contactors
Open Control
C30CN Mechanically Held
Amps
Continuous
30
20
Horsepower
Horsepower
10
15
Number
of Cables
1
2
1 or 2
1
1 or 2
1
2
3
5
Poles
1-Phase
347V AC 600V AC
600V AC 600V AC
277V AC 480V AC
600V AC 600V AC
3-Phase
Wire Range
(Solid or Stranded)
14 – 8 AWG
14 – 8 AWG
18 – 14 AWG
22 – 12 AWG
22 – 12 AWG
Control Circuit Characteristics
Table 37-16. Coil
Table 37-17. Control Module
Table 37-18. Other Control Module
Characteristics
Auxiliary Contacts Rating:
A600, 24V DC, 24 VA
Ambient Temperature:
-13 to 104°F (-25 to 40°C)
Mounting Position:
Vertical 3-point mounting only.
Description
Inrush
Sealed
Input
Voltage
115 – 120V AC
200 – 277V AC
Description
Minimum pulse duration
(3-wire control module)
Maximum allowable
leakage current
EMI
Surge transient peak
Frequency Range
24V AC
12 – 24V DC
Steady State
Current @ Rated
Voltage (mA)
42
80
83
91
Wire
Temperature
75°C Cu
75°C Cu
60°/75°C Cu
60°/75°C Cu
60°/75°C Cu
VA
248 VA
28 VA
250 ms
1.8 mA
Specification
35 V/m
6 kV
40 – 70 Hz
Maximum
VA
12
30
2
5
37-9
37

Related parts for C30CNE20A0