C500MP102EV3 Omron, C500MP102EV3 Datasheet - Page 91

no-image

C500MP102EV3

Manufacturer Part Number
C500MP102EV3
Description
K-TYPE PC MEMORY RACK
Manufacturer
Omron
Datasheet

Specifications of C500MP102EV3

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
JUMP and JUMP END – JMP(04) and JME(05)
5-8
80
Example
Limitations
Description
JUMP and JUMP END – JMP(04) and JME(05)
0100
0000
0001
0002
0003
0005
0004
The following diagram shows IL(02) being used twice with one ILC(03).
When the execution condition for the first IL(02) is OFF, TIM 11 will be reset
to 1.5 s, CNT 01 will not be changed, and 0502 will be turned OFF. When the
execution condition for the first IL(02) is ON and the execution condition for
the second IL(02) is OFF, TIM 11 will be executed according to the status of
0001, CNT 01 will not be changed, and 0502 will be turned OFF. When the
execution conditions for both the IL(02) are ON, the program will execute as
written.
Jump numbers 01 through 08 may be used only once in JMP(04) and once in
JME(05), i.e., each can be used to define one jump only. Jump number 00
can be used as many times as desired.
JMP(04) is always used in conjunction with JME(05) to create jumps, i.e., to
skip from one point in a ladder diagram to another point. JMP(04) defines the
point from which the jump will be made; JME(05) defines the destination of
the jump. When the execution condition for JMP(04) in ON, no jump is made
and the program is executed as written. When the execution condition for
JMP(04) is OFF, a jump is made to the JME(05) with the same jump number
and the instruction following JME(05) is executed next.
If the jump number for JMP(04) is between 01 and 08, jumps, when made,
will go immediately to JME(05) without executing any instructions in between.
The status of timers, counters, bits used in OUT, bits used in OUT NOT, and
all other status controlled by the instructions between JMP(04) and JMP(05)
Ladder Symbols
Ladder Symbols
JMP(04) N
JME(05) N
CP
R
TIM 11
ILC(03)
CNT 01
0502
IL(02)
IL(02)
IR 10
#0015
1.5 s
Address Instruction
0000
0001
0002
0003
0004
0005
0006
0007
0008
0009
0010
0011
0012
LD
IL(02)
LD
TIM
LD
IL(02)
LD
AND NOT
LD
CNT
LD
OUT
ILC(03)
Definer Values
Definer Values
N: Jump number
N: Jump number
# (00 to 08)
# (00 to 08)
#
Operands
Section 5-8
0000
0001
0015
0002
0003
0004
0100
0005
0502
01
10
11

Related parts for C500MP102EV3