C500MP102EV3 Omron, C500MP102EV3 Datasheet - Page 97

no-image

C500MP102EV3

Manufacturer Part Number
C500MP102EV3
Description
K-TYPE PC MEMORY RACK
Manufacturer
Omron
Datasheet

Specifications of C500MP102EV3

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Timer and Counter Instructions
5-11-2
86
Example 5:
Flicker Bits
Limitations
Description
0000
TIM 01
TIM 01
0205
0000
TIM 02
HIGH-SPEED TIMER – TIMH(15)
1.0 s
Ladder Symbol
1.5 s
1.0 s
Bits can be programmed to turn ON and OFF at a regular interval while a
designated execution condition is ON by using TIM twice. One TIM functions
to turn ON and OFF a specified bit, i.e., the completion flag of this TIM turns
the specified bit ON and OFF. The other TIM functions to control the opera-
tion of the first TIM, i.e., when the first TIM’s completion flag goes ON, the
second TIM is started and when the second TIM’s completion flag goes ON,
the first TIM is started.
An easier but more limited method of creating a flicker bit is to AND one of
the SR area clock pulse bits with the execution condition that is to be ON
when the flicker bit is operating. Although this method does not use TIM, it is
included here for comparison. This method is more limited because the ON
and OFF times must be the same and they depend on the clock pulse bits
available in the SR area.
SV may be between 00.02 and 99.99 seconds. (Actually settings of 00.00
and 00.01 are allowed, but 00.00 is meaningless and 00.01 is not reliable.)
The decimal point of SV is not input.
Each TC number can be used as the definer in only one timer or counter in-
struction.
A cycle time of greater than 10 ms will affect the accuracy of the timer.
TIMH(15) operates the same as TIM except that TIMH measures in units of
0.01 second.
Refer to 5-11-1 TIMER – TIM for operational details and examples. All as-
pects except for the above considerations are the same.
1.5 s
TIMH(15) N
SV
TIM 01
TIM 02
#0010
#0015
0205
1.0 s
1.5 s
SV: Set value (word, BCD)
Operand Data Areas
Definer Values
# (00 though 47 )
Address Instruction
N: TC number
0000
0001
0002
0003
0004
0005
0006
IR, HR, #
LD
AND
TIM
LD
TIM
LD
OUT
TIM
#
TIM
#
TIM
Section 5-11
Operands
0000
0010
0015
0205
02
01
01
02
01

Related parts for C500MP102EV3