PAXCK000 Red Lion Controls, PAXCK000 Datasheet - Page 4

Digital Multifunction Timer

PAXCK000

Manufacturer Part Number
PAXCK000
Description
Digital Multifunction Timer
Manufacturer
Red Lion Controls
Type
Clock/Timerr
Datasheet

Specifications of PAXCK000

Time Range
0.001sec To 1hr
Power Consumption
18VA
Supply Voltage Ac, Min
85V
Signal Input Type
Pulse
Supply Voltage Max
250VAC
Time Range Max
999999h
Character Size
0.56"
Accuracy
±0.01% %
Connection Type
Cage-Clamp
Cut Out, Panel
3.62×1.77 "
Digit Height
0.56
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Display Resolution
0.001 Sec. (Minimum Digit), 1 hr. (Single Digit)
Display Type
LED
Function
Real Time Clock/Timer
Humidity
0 to 85% (Max.) RH
Isolation Voltage
2300 V (RMS)
Length, Stripping
0.3 in. Wire
Memory Type
Non-Volatile EEPROM
Number Of Digits
6
Power, Rating
18 VA
Primary Type
Electronic
Range, Measurement
0 to 999999
Special Features
Programmable Function Keys
Standards
cULus Listed, CSA Certified
Temperature, Operating
0 to +50 °C
Termination
Cage Clamp
Torque
4.5 in.-lbs
Voltage, Range
85 to 250 VAC
Voltage, Supply
85 to 250 VAC
Four Separate Displays
Timer, Counter, Real-Time Clock and Date
Display Font Color
Red
No. Of Digits / Alpha
6
Supply Voltage Ac, Max
250V
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
Adding Option Cards
in cards. The details for each plug-in card can be reviewed in the specification
section below. Only one card from each function type can be installed at one time.
The function types include Setpoint Alarms (PAXCDS), Communications
(PAXCDC), and Real-Time Clock Card (PAXRTC). The plug-in cards can be
installed initially or at a later date.
COMMUNICATION CARDS (PAXCDC)
series. Only one of these cards can be installed at a time. When programming
the unit via RLCPro, a Windows
must be used.
SERIAL COMMUNICATIONS CARD
DEVICENET™ CARD
MODBUS CARD
PROFIBUS-DP CARD
PROGRAMMING SOFTWARE
configuration of the PAX
menu commands, that make it easy to program the meter. The meter’s program
can then be saved in a PC file for future use. A PAX
required to program the meter using the software.
O
PAXCDC10 - RS485 Serial (Terminal)
PAXCDC1C - RS485 Serial (Connector)
PAXCDC20 - RS232 Serial (Terminal)
PAXCDC2C - RS232 Serial (Connector)
The PAX and MPAX series meters can be fitted with up to three optional plug-
A variety of communication protocols are available for the PAX and MPAX
Type: RS485 or RS232
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Data: 7/8 bits
Baud: 300 to 19,200
Parity: No, Odd or Even
Bus Address: Selectable 0 to 99, Max. 32 meters per line (RS485)
Transmit Delay: Selectable for 2 to 50 msec or 50 to 100 msec (RS485)
Compatibility: Group 2 Server Only, not UCMM capable
Baud Rates: 125 Kbaud, 250 Kbaud, and 500 Kbaud
Bus Interface: Phillips 82C250 or equivalent with MIS wiring protection per
Node Isolation: Bus powered, isolated node
Host Isolation: 500 Vrms for 1 minute (50 V working) between DeviceNet™
Type: RS485; RTU and ASCII MODBUS modes
Isolation To Sensor & User Input Commons: 500 Vrms for 1 minute.
Baud Rates: 300 to 38,400.
Data: 7/8 bits
Parity: No, Odd, or Even
Addresses: 1 to 247.
Transmit Delay: Programmable; See Transmit Delay explanation.
Fieldbus Type: Profibus-DP as per EN 50170, implemented with Siemens
Conformance: PNO Certified Profibus-DP Slave Device
Baud Rates: Automatic baud rate detection in the range 9.6 Kbaud to 12 Mbaud
Station Address: 0 to 126, set by the master over the network. Address stored
Connection: 9-pin Female D-Sub connector
Network Isolation: 500 Vrms for 1 minute (50 V working) between Profibus
The Crimson
Working Voltage: 50 V. Not Isolated from all other commons.
DeviceNet™ Volume I Section 10.2.2.
and meter input common.
Working Voltage: 50 V. Not isolated from all other commons.
SPC3 ASIC
in non-volatile memory.
network and sensor and user input commons. Not isolated from all other
commons.
PTIONAL
WARNING: Disconnect all power to the unit before
installing Plug-in cards.
®
software is a Windows
®
meter from a PC. Crimson offers standard drop-down
®
P
based program, the RS232 or RS485 Cards
LUG
PAXCDC30 - DeviceNet
PAXCDC40 - Modbus (Terminal)
PAXCDC4C - Modbus (Connector)
PAXCDC50 - Profibus-DP
®
based program that allows
-
IN
®
serial plug-in card is
C
ARDS AND
4
SETPOINT CARDS (PAXCDS)
cards. Only one of these cards can be installed at a time. (Logic state of the
outputs can be reversed in the programming.) These plug-in cards include:
DUAL RELAY CARD
QUAD RELAY CARD
QUAD SINKING OPEN COLLECTOR CARD
QUAD SOURCING OPEN COLLECTOR CARD
The PAX and MPAX series has 4 available setpoint alarm output plug-in
Type: Two FORM-C relays
Isolation To Timer & User Input Commons: 2300 Vrms for 1 min.
Contact Rating:
Life Expectancy: 100 K cycles min. at full load rating. External RC snubber
Response Time: 5 msec. nominal with 3 msec. nominal release
Timed Output Accuracy: ±0.01% -10 msec.
Type: Four FORM-A relays
Isolation To Timer & User Input Commons: 2300 Vrms for 1 min.
Contact Rating:
Life Expectancy: 100K cycles min. at full load rating. External RC snubber
Response Time: 5 msec. nominal with 3 msec. nominal release
Timed Output Accuracy: ±0.01% -10 msec.
Type: Four isolated sinking NPN transistors.
Isolation To Timer & User Input Commons: 500 Vrms for 1 min.
Rating: 100 mA max @ V
Response Time: 400 µsec. nominal with 2 msec. nominal turnoff
Timed Output Accuracy: ±0.01% -10 msec.
Type: Four isolated sourcing PNP transistors.
Isolation To Timer & User Input Commons: 500 Vrms for 1 min.
Rating: Internal supply: 24 VDC ± 10% , 30 mA max. total
Response Time: 400 µsec. nominal with 2 msec. nominal turnoff
Timed Output Accuracy: ±0.01% -10 msec.
PAXCDS10 - Dual Relay, FORM-C, Normally open & closed
PAXCDS20 - Quad Relay, FORM-A, Normally open only
PAXCDS30 - Isolated quad sinking NPN open collector
PAXCDS40 - Isolated quad sourcing PNP open collector
Working Voltage: 240 Vrms
One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive load),
Total current with both relays energized not to exceed 5 amps
extends relay life for operation with inductive loads
Working Voltage: 250 Vrms
One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load), 1/10
Total current with all four relays energized not to exceed 4 amps
extends relay life for operation with inductive loads
Working Voltage: 50 V.
Working Voltage: 50 V.
1/8 HP @120 VAC, inductive load
HP @ 120 VAC, inductive load
External supply: 30 VDC max., 100 mA max. each output
A
CCESSORIES
SAT
Not Isolated from all other commons.
Not Isolated from all other commons.
= 0.7 V max. V
MAX
= 30 V

Related parts for PAXCK000