CS1W-CRM21 Omron, CS1W-CRM21 Datasheet - Page 189

no-image

CS1W-CRM21

Manufacturer Part Number
CS1W-CRM21
Description
CS1 CompoNet Master
Manufacturer
Omron
Datasheet

Specifications of CS1W-CRM21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Note
When the PLC is connected online, the display will show green and red indicators on
the Units that indicate errors with Units registered in the routing tables.
The following table shows the meaning of the display's indicators.
Green Indicator:
Unit exists in routing
tables.
Note: These indicators
Red Indicator:
Error with Unit
Green indicator
Red indicator
are not related
to the actual
LED Indicators
on the front of
the Unit.
The Unit with the unit number set in the routing tables is
actually mounted in the PLC Backplane.
One of the following errors was detected in the Unit with the
unit number set in the routing table.
1. The Unit's node address is duplicated.
2. The Unit's node address is out-of-range.
3. There is an error in the routing table settings.
3-3 Maintenance after Network Configuration
3-3-2 Editing the FINS Local Network Tables
3-33