CS1W-CRM21 Omron, CS1W-CRM21 Datasheet - Page 402

no-image

CS1W-CRM21

Manufacturer Part Number
CS1W-CRM21
Description
CS1 CompoNet Master
Manufacturer
Omron
Datasheet

Specifications of CS1W-CRM21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
10-2
10-2-1
10-2 Echoback Test between Nodes
10-2-1
10-2-2
10-2-3
10-22
Echoback Test between Nodes
Overview
Overview
Start Methods
PLC Internode Echoback Test Dialog Box
The Internode Echoback Test between PLC Nodes tool is used to execute echoback
tests between specified networks and nodes and the CX-Integrator. Echoback tests
can be executed for Ethernet, Controller Link, SYSMAC LINK, or DeviceNet networks.
A specified data length (unit: bytes) is sent to a specified network and node. The data
is sent back as is (echoback), and the results are compared. If the data agrees, it is
judged a success. If not, it is judged a failure. This allows the communications load
conditions between the computer and specified nodes to be tested.
Either of the following two methods can be used to start an echoback test:
Method 1: While online, open the Online Connection Information Window, right-click
the target PLC or Unit, and select Echoback test between PLC nodes from the
pop-up menu.
Method 2: While online, select Tools - Echoback test between PLC nodes.
The various items in the PLC Internode Echoback Test Dialog Box are explained
below.
Target
Test
Configuration
Connection
Status
Test Results
Field
Network
Node
Data Length
Times to
Repeat
Frequency is
not specified
Response
wait time
Network
Node
Model
Elapsed time
Tests run
Item
Input the network address. Range: 1 to 127.
Input the node address. Range: 1 to 254.
Input the number of bytes of data to be sent between
nodes. Range: 1 to 256.
Input the number of times to repeat the test.
Range: 1 to 255.
Check this item to repeat the tests limitlessly.
Input the time to wait for the echo request packet.
Range: 1 to 30.
Displays the target network address.
Displays the target node address.
Displays the target model.
Displays the online status.
Displays the time elapsed for the test.
Displays the number of times the test has been run.
Contents