Specifications of H3DE-S2 AC/DC24-230

Brand/series
H3DE
Contact Form
DPDT
Current, Rating
5 A
Function
Timing
Mounting Type
DIN Rail
Relay Type
Electro Mechanical
Timer Type
Multi-Function
Voltage, Control
230 VAC/VDC
Voltage, Rating
250/30 VAC/VDC
Supply Voltage
24-230 VAC/VDC
Control Output
SPDT Time Limit (M1/S1), DPDT Time Limit SPDT and Instantaneous SPDT (M2/S2)
Lead Free Status / Rohs Status
RoHS Compliant part
J POWER SUPPLIES
The H3DE Series is provided with a transformerless power
supply system. An electric shock may be received if the input
terminal or the output type selector switch is touched while power
is being supplied.
Use the bar terminal for wiring the H3DE. Using a stranded-wire
terminal may cause a short-circuit due to a stray wire entering
into the Timer.
Both AC and DC power supplies can be connected to the power
input terminals without regarding polarity.
With the H3DE only, a DC power supply must be connected to
the power input terminals as designated according to the polarity
of the terminals.
A DC power supply can be connected if its ripple factor is 20% or
less and the mean voltage is within the rated operating voltage
range of the Timer.
Connect the power supply voltage through a relay or switch in
such a way that the voltage reaches a fixed value at once or the
Timer may not be reset or a timer error could result.
For the power supply of an input device, use an isolating
transformer, of which the primary and secondary windings are
mutually isolated and the secondary winding is not grounded.
12
Circuit
Start
input
B1
H3DE
A1
A2
Isolation transformer is required.
Power supply
J MOUNTING CLEARANCE
If the load current is continuously being supplied to the Timer for
a long period of time, be sure to provide the mounting clearance
as shown in the figure below. If used under the conditions other
than those specified below, the life of internal components may
be shortened due to an excessive rise in the internal
temperature.
J SWITCHING CURRENT VS.
Note: Measurement Condition: Input voltage of 230 VAC.
AMBIENT TEMPERATURE
(WHEN MOUNTING TWO OR MORE
H3DE UNITS SIDE-BY-SIDE)
70
60
50
40
30
20
0
H3DE
1
t
2
H3DE
t: Mounting clearance (mm)
3
4
t
H3DE
5
Mounting
clearance: 5 mm
Mounting clearance:
50 mm min.
Mounting
clearance: 10 mm
Mounting
clearance: 0 mm
Load current (A)
Maximum range of
operating ambient
temperature
DIN track