H3DE-S2 AC/DC24-230 Omron Automation, H3DE-S2 AC/DC24-230 Datasheet - Page 3

no-image

H3DE-S2 AC/DC24-230

Manufacturer Part Number
H3DE-S2 AC/DC24-230
Description
Timer, Standard Type, DPDT, Analog, 0.1 Second to 120 Hours, 24-230 VAC/VDC
Manufacturer
Omron Automation
Datasheet

Specifications of H3DE-S2 AC/DC24-230

Brand/series
H3DE
Contact Form
DPDT
Current, Rating
5 A
Function
Timing
Mounting Type
DIN Rail
Relay Type
Electro Mechanical
Timer Type
Multi-Function
Voltage, Control
230 VAC/VDC
Voltage, Rating
250/30 VAC/VDC
Supply Voltage
24-230 VAC/VDC
Control Output
SPDT Time Limit (M1/S1), DPDT Time Limit SPDT and Instantaneous SPDT (M2/S2)
Lead Free Status / Rohs Status
RoHS Compliant part
J CHARACTERISTICS
Note: 1. With the H3DE-Mj, if the voltage exceeds 26.4 VAC/DC, the following hold at signal OFF for C, D, and G modes:
Accuracy of operating time
Setting error
Signal input time
Voltage influence
Temperature influence
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Contact material
Impulse withstand voltage
Noise immunity
Static immunity
Life expectancy
EMC
Enclosure rating
Weight
2. For reference : A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1).
Accuracy of operating time: ±1% ±50 ms max. at 1.2-s range
Setting error: ±10% +100/- -50 ms max.
Signal input time: 100 ms min.
A maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
±1% max. of FS (±1% ±10 ms max. at 1.2-s range) (See Note 1.)
±10% ±50 ms max. of FS (See Note 1.)
50 ms min. (See Note 1.)
±0.5% max. of FS (±0.5% ±10 ms max. at 1.2-s range)
±2% max. of FS (±2% ±10 ms max. at 1.2-s range)
100 MΩ min. at 500 VDC
Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC for 1 min.
Between control output terminals and operating circuit: 2,000 VAC for 1 min.
Between contacts of different polarities: 2,000 VAC for 1 min.
Between contacts not located next to each other: 1,000 VAC for 1 min.
Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Malfunction: 100 m/s
Destruction: 1,000 m/s
AgNi+gold plating (Use the G6RN-1 at 12 VDC.)
3 kV (between power terminals)
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV
Malfunction: 4 kV
Destruction: 8 kV
Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
(See Note 2.)
EMI
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Harmonic Current: EN61000-3-2
Voltage Fluctuation and Flickering EN61000-3-3
EMS
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3);
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3);
1 kV control port with capacitive clamp (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3);
1 kV differential mode (level 3)
IP30 (Terminal block: IP20)
120 g
2
(approximately 10G)
2
(approximately 100G)
3

Related parts for H3DE-S2 AC/DC24-230