EDS11-164A FUJI [Fuji Electric], EDS11-164A Datasheet

no-image

EDS11-164A

Manufacturer Part Number
EDS11-164A
Description
Manufacturer
FUJI [Fuji Electric]
Datasheet
PX series
Digital temperature
Controller
SPECIFICATIONS
With front dimensions of 48×48mm, this socket type tem-
perature controller enables On-Off control, PID control or
8-step ramp/soak function, using thermocouple, resistance
bulb or DC1 to 5V signal as input.
Though small-sized, it can be equipped with a variety of
functions.
FEATURES
1. PID with auto-tuning, PID self-tuning and fuzzy control are
2. Front side waterproof specification in conformity with
3. Two alarms are equipped, and 8-step ramp/soak function
1. General specifications
Power supply
voltage
Power
consumption
Insulation resistance
Dielectric strength
Input impedance
Allowable signal
source resistance
Allowable wiring
resistance
Reference junction
compensation accuracy
Input value correction
Set value correction
Input filter
Noise reduction ratio
DATA SHEET
installed as standard.
NEMA4X (standard).
can be installed as an option.
100 V (-15%) to 240 V (+10%) AC, 50/60 Hz
or 24 V (±10%) AC 50/60 Hz, 24 V (±10%) DC
When using 100 V AC : 8 VA or less
When using 220 V AC : 10 VA or less
When using 24 V AC/DC : 10VA
20 MΩ or more (500 V DC)
Power supply-ground ... 1500 V AC for 1 min
Power supply-others ... 1500 V AC for 1 min
Ground-relay output ... 1500 V AC for 1 min
Ground-alarm output ... 1500 V AC for 1 min
Others ... 500 V AC for 1 min
Thermocouple: 1 MΩ or more
Voltage: 450 kΩ or more
Current: 250Ω (external resistor)
Thermocouple: 100Ω or less
Voltage: 1 kΩ or less
Resistance bulb: 10Ω or less per wire
±1°C (at 23°C)
±10% of measuring range
±50% of measuring range
0 to 900.0 sec settable in 0.5 sec steps
(first order lag filter)
Normal mode noise (50/60 Hz): 50 dB or more
Common mode noise (50/60 Hz): 140 dB or more
Socket Type
MICRO-CONTROLLER X
MICRO-CONTROLLER X
2. Control function of standard type
3. Input section
4. Output section of standard type (control output 1)
Control action
Proportional band (P)
Integral time (I)
Differential time (D)
On/off action if P = 0. Proportional action when I, D = 0.
Proportional cycle
Hysteresis width
Anti-reset windup
Input sampling cycle
Control cycle
Input signal
Measuring range
Burnout
Control output 1
(48mm×48mm)
PID control (with auto tuning, self-tuning)
Fuzzy control (with auto tuning)
Self tuning
0 to 999.9% of measuring range settable in
0.1% step
0 to 3200 sec settable in 1 sec step
0 to 999.9 sec settable in 0.1 sec step
1 to 150 sec settable in 1 sec step
Only for relay contact output or SSR/SSC drive
output
0 to 50% of measuring range
For On/off action only
0 to 100% of measuring range
Automatically validated at auto tuning
0.5 sec
0.5 sec
Thermocouple : J, K, R, B, S, T, E, N, PLII
Resistance bulb : Pt100
Voltage, current: 1 to 5 V DC, 4 to 20 mA DC
(Apply current input after connecting the
furnished 250Ω resistor to input terminal.)
See measuring range table (Table1)
For thermocouple or resistance bulb input
Control output upper/lower are selectable
Select one as follows
Relay contact: SPDT contact:
SSR / SSC drive (Voltage pulse):
4 to 20mA DC: Allowable load resistance 600Ω
or less
220V AC/30V DC, 3A (resistive load)
Mechanical life 10 million operations (no load)
Electrical life 100,000 operations (rated load)
Minimum switching current 100mA (24V DC)
ON: 17 to 25 V DC
OFF: 0.5V DC or less
Max. current: 20mA or less
Date
EDS11-164a
SOCKET
PXR4
Apr. 1, 2011

Related parts for EDS11-164A

EDS11-164A Summary of contents

Page 1

... Mechanical life 10 million operations (no load) Electrical life 100,000 operations (rated load) Minimum switching current 100mA (24V DC) SSR / SSC drive (Voltage pulse): ON OFF: 0. less Max. current: 20mA or less 4 to 20mA DC: Allowable load resistance 600Ω or less PXR4 SOCKET EDS11-164a Date Apr. 1, 2011 ...

Page 2

PXR4 SOCKET 5. Operation and display section Parameter setting Digital setting by 3 keys method With key lock function Display Process value/set value Independent display 4 digits, 7-segment LED Status display LED Control output, process alarm output Setting accuracy 0.1% ...

Page 3

PXR Model Code Configuration Digit Specification 4 <Front dimensions> 48 × 48mm 5 <Input signal> Thermocouple °C Thermocouple °F Resistance bulb Pt100 3-wire type I (°C) Resistance bulb Pt100 3-wire type I (° 20mA ...

Page 4

PXR4 SOCKET Scope of delivery Scope of delivery Controller, panel mounting bracket, watertight packing, instruction manual (as ordered), socket (as ordered), (for current input) Option 250Ω ±0.1% Shunt resistor Model: ZZPPXR1-A190 Insulation block diagram Power supply section Measurement input Relay ...

Page 5

OUTLINE DIAGRAM (Unit: mm) 48 Water-proof packing Panel cutout size (Unit: mm) +0 63min. Mounting frame 93.7 79.5 84.7 Panel 70 Side stick mounting (n units) (48 x N-3) Note: Waterproof is ...

Page 6

PXR4 SOCKET CONNECTION DIAGRAM (1) With alarm functions 11-pin socket • When compatible with PXW4/PXZ4/PXV4 thermocouple input terminal (When either one of the following is selected for the 5th digit of the code symbols: “T, ” “R, ” “W, ” ...

Page 7

Without alarm functions 8-pin socket • When compatible with PXW4/PXZ4/PXV4 thermocouple input terminal (When either one of the following is selected for the 5th digit of the code symbols: “T, ” “R, ” “W, ” “A” and “B”) Note ...

Page 8

PXR4 SOCKET SOCKET OUTLINE DIAGRAM (Unit: mm) Without alarm TP48SB TYPE (FOR PANEL MOUNTING) φ With alarm TP411X TYPE (FOR RAIL MOUNTING) TERMINAL SCREW M3.5× 2-φ4 HOLE 10 ...