TLA21000 Red Lion Controls, TLA21000 Datasheet
TLA21000
Specifications of TLA21000
Related parts for TLA21000
TLA21000 Summary of contents
Page 1
MODEL TLA - TEMPERATURE LIMIT ALARM FM APPROVED GENERAL DESCRIPTION The TLA is a Factory Mutual approved temperature limit alarm, intended to provide an independent shutdown for thermal processes. The TLA accepts signals from a variety of temperature sensors (thermocouple ...
Page 2
GENERAL SPECIFICATIONS 1. DISPLAY: 2 line by 4-digit LED Upper (Main) Display: 0.4" (10.2 mm) high red LED Lower (Secondary) Display: 0.3" (7.6 mm) high green LED Display Messages: “OLOL” - Appears when measurement exceeds + sensor range. “ULUL” - ...
Page 3
... Life Expectancy: 100,000 cycles at max. load rating. (Decreasing load increases life expectancy.) 2. LIMIT OUTPUT: TLA21000: Form-C relay; TLA11100: Form-A relay. Selectable for high or low trip activation. If the process temperature goes above the limit setpoint for a high trip, or below the limit setpoint for a low trip, the limit relay will de-energize to initiate a process shutdown ...
Page 4
INSTALLING THE TLA The TLA meets NEMA 4X/IP65 requirements for indoor use to provide a watertight seal in steel panels with a minimum thickness of 0.09 inch, or aluminum panels with a minimum thickness of 0.12 inch. The units ...
Page 5
WIRING THE TLA After the unit has been mechanically mounted ready to be wired. All wiring connections are made to the rear screw terminals. When wiring the unit, use the numbers on the label and those embossed ...
Page 6
FRONT PANEL DESCRIPTION The front panel bezel material is flame and scratch resistant, tinted plastic that meets NEMA 4X/IP65 requirements, when properly installed. Continuous exposure to direct sunlight may accelerate the aging process of the bezel. The bezel should ...
Page 7
CONFIGURATION PARAMETER MODULES The Configuration Parameter modules are accessed by pressing the UP button from CNFP in the Parameter Mode. The UP or DOWN buttons can be pressed to move to the desired Parameter Module. The P button is then ...
Page 8
C M ONFIGURE ODULE DISPLAY PARAMETER PASS Password AL * Alarms #1 and #2 access level FPrS Front panel reset * Model Number Dependent ONFIGURE ODULE DISPLAY PARAMETER Act1 Alarm 1 action mode rSt1 Alarm 1 reset mode ...
Page 9
C M ONFIGURE ODULE DISPLAY PARAMETER CodE Factory service function code USER PARAMETER VALUE CHART TLA Number _____________ MNEMONIC PARAMETER pass Password sp Limit Setpoint aL-1 Alarm 1 Value AL-2 Alarm 2 Value 1-IN Input Parameters MNEMONIC PARAMETER tYPE Input ...
Page 10
LIMIT OUTPUT ACTION The limit output is selectable for high or low trip activation. If the process temperature goes above the limit setpoint for a high trip, or below the limit setpoint for a low trip, the limit relay will ...
Page 11
Alarm Reset Sequence CALIBRATION CHECKS The instrument has been fully calibrated at the factory for all input types. If the unit appears to be indicating or controlling incorrectly, see the Troubleshooting section before attempting this procedure. If the TLA is ...
Page 12
C ALIBRATION When re-calibration is required (generally every two years), this procedure should be performed by qualified technicians using appropriate equipment. Equipment source accuracy of 0.03% or better is required. The procedure consists of: applying accurate mV signals, setting ...
Page 13
T ROUBLESHOOTING The majority of problems can be traced to improper connections or incorrect set-up parameters. Be sure all connections are clean and tight, that the correct output board is fitted, and that the set-up parameters are correct. PROBLEMS ...
Page 14
I NSTALLING AN The TLA is supplied with an output board installed. Replacing Output Board 1. Remove the bezel assembly. 2. Lift up on the top bezel board latch while gently pulling out on the bezel/ display board assembly. ...