TLA21000

Manufacturer Part Number
TLA21000
Description
Form-C Limit Relay W/1 Alarm
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheet

Specifications of TLA21000

Brand/series
TLA Series
Contact Form
SPST/SPDT
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Mounting Type
Panel
Number Of Outputs
1
Output Type
Relay
Power, Rating
8 VA
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE, FM
Temperature, Ambient
0 to +50 °C (Max.)
Termination
Screw
Voltage, Rating
120⁄240 VAC
Voltage, Supply
85 to 250 VAC
Panel Cutout
1.77" × 1.77" (1⁄16 DIN)
Power Requirements
85-250 VAC
Sealing
NEMA 4X/IP65
Operating Temperature
0°C to +50°C
Lead Free Status / Rohs Status
RoHS Compliant part
CONFIGURATION PARAMETER MODULES
from CNFP in the Parameter Mode. The UP or DOWN buttons can be pressed to
move to the desired Parameter Module. The P button is then pressed to enter into
that module. The main (top) display will be the parameter, and the secondary
(bottom) display will be the parameter value. The UP or DOWN buttons are used
to modify the desired parameter value, and the P button enters the new value, and
moves to the next parameter. The TLA responds to the new values after the P
C
C
The Configuration Parameter modules are accessed by pressing the UP button
ONFIGURE
ONFIGURE
DISPLAY
DISPLAY
SCAL
SPLO
SPHI
tYPE
dCPt
SHFt
FLtr
LiAc
Input Type
Temperature Scale
Temperature Resolution
Digital Input Filtering and
Display Update
Input Signal Shift
(correction offset)
Limit Setpoint Lower Limit
Limit Setpoint Upper Limit
Limit Output Trip Action
PARAMETER
PARAMETER
M
M
ODULE
ODULE
4 - most input filtering and slower 500
msec display update rate (outputs still
1 - I
2 - O
update at 100 msec rate)
r385 - 385 curve RTD
r392 - 392 curve RTD
3 - most input filtering
0 - least input filtering
(FACTORY SETTING)
(FACTORY SETTING)
rLIN - Linear ohms
tc-E - Type E TC
tc-K - Type K TC
tc-S - Type S TC
tc-N - Type N TC
tc-b - Type B TC
tc-J - Type J TC
tc-r - Type R TC
LIN - Linear mV
LO - Low Acting
tc-t - Type T TC
HI - High Acting
1 or 0.1 degree
1 or 0.1 degree
1 or 0.1 degree
-999 to 9999
-999 to 9999
-999 to 9999
NPUT
°F or °C
0 or 0.0
RANGE
RANGE
UTPUT
(9999)
0 to 4
(tc-J)
(°F)
(HI)
(0)
(1)
(0)
(0)
P
ARAMETERS
P
7
ARAMETERS
button is pressed, however, the change is not committed to permanent memory
until the TLA is returned to the Normal Display Mode. If power loss occurs before
returning to the Normal Display Mode, the new values must be entered again. At
the end of each module, the TLA will go back to CNFP. Other Parameter Modules
can be accessed by pressing the UP or DOWN buttons, or pressing P will return
to the Normal Display Mode.
displayed when the appropriate options are installed or programmed.
Select from the list of various thermocouple and RTD sensors.
Select either degrees Fahrenheit (F) or degrees Celsius (C). If
changed, be sure to check all parameters.
Select either 1 or 0.1 degree resolution. If changed, be sure to
check all parameters.
Select the relative degree of input signal filtering and display update
rate. The filter is an adaptive digital filter that discriminates between
measurement noise and actual process changes. Therefore, the
influence on step response time is minimal. If the signal is varying
too greatly due to measurement noise, increase the filter value.
Conversely, if the fastest TLA response is desired, decrease the
filter value.
If the TLA temperature disagrees with a reference temperature
instrument or if the temperature sensor has a known calibration, the
TLA temperature can be compensated by a correction offset. The
following equation expresses the relationship: Desired Display Temp
= (TLA Temp) + SHFt. Normally set to 0.
The TLA has programmable high and low setpoint limit values to
restrict the setting range of the limit setpoint. Set the limit values so
that the temperature setpoint value cannot be set outside the safe
operating area of the process. SPHI must be above SPLO.
The limit output is selectable for high or low trip activation. If the
process temperature goes above the limit setpoint for a high trip, or
below the limit setpoint for a low trip, the limit relay will de-energize
to initiate a process shutdown. See the Limit Output Action section
for details.