TLA21000 Red Lion Controls, TLA21000 Datasheet - Page 10

no-image

TLA21000

Manufacturer Part Number
TLA21000
Description
Form-C Limit Relay W/1 Alarm
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheet

Specifications of TLA21000

Brand/series
TLA Series
Contact Form
SPST/SPDT
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Mounting Type
Panel
Number Of Outputs
1
Output Type
Relay
Power, Rating
8 VA
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE, FM
Temperature, Ambient
0 to +50 °C (Max.)
Termination
Screw
Voltage, Rating
120⁄240 VAC
Voltage, Supply
85 to 250 VAC
Panel Cutout
1.77" × 1.77" (1⁄16 DIN)
Power Requirements
85-250 VAC
Sealing
NEMA 4X/IP65
Operating Temperature
0°C to +50°C
Lead Free Status / Rohs Status
RoHS Compliant part
LIMIT OUTPUT ACTION
temperature goes above the limit setpoint for a high trip, or below the limit
setpoint for a low trip, the limit relay will de-energize to initiate a process
shutdown. The limit output cannot be reset until the process temperature returns
to the proper operating range; manual reset is required. The following action
figures describe the status of the limit output and the front panel indicators for
various over/under setpoint, and reset conditions. Reset is either by the front
panel R button, if enabled, or by the Remote Reset input, terminal #6. Refer to
Configure Module 2 - Output Parameters for details of configuring the limit
output. Refer to Configure Module 3 - Lockout Parameters for details of
configuring the front panel Reset button.
panel indicator for various over/under temperature conditions. The alarm output
wave form is shown with the output in the automatic reset mode. Select the
5.0 A
The limit output is selectable for high or low trip activation. If the process
The alarm action figures describe the status of the alarm output and the front
LARMS
(O
PTIONAL
)
10
alarm action with care -- in some configurations, the front panel indicator (LED)
might be OFF while the output is ON. Refer to Configure Module 4 - Alarm
Parameters for details of configuring the alarms.
High Trip Action
Low Trip Action