DRT2-ID32BV-1 Omron, DRT2-ID32BV-1 Datasheet - Page 58

no-image

DRT2-ID32BV-1

Manufacturer Part Number
DRT2-ID32BV-1
Description
32 In Vert MIL Connector PNP
Manufacturer
Omron
Datasheet

Specifications of DRT2-ID32BV-1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
DeviceNet Remote I/O Communications
■ Example of Allocation Using Method 2
The Generic Status Flags are as follows:
0
1
2
3
4
5
Bit
Basic Unit's I/O Power Status Flag
0: I/O power supply ON
1: I/O power supply OFF
Expansion Unit's I/O Power Status Flag
0: I/O power supply ON
1: I/O power supply OFF
Network Power Voltage Drops Flag
0: Normal (Higher than set monitor value)
1: Error (Same as or lower than set monitor value)
Unit Maintenance Flag
0: Within range (Lower than set monitor value)
1: Out of range (Same as or higher than set monitor value)
Sensor Disconnected Flag (Screw-less Clamp Input and I/O Terminals, and
Environment-resistive Input Terminals only) or External Load Disconnected
Flag (Screw-less Clamp Output and I/O Terminals only)
0: Connected (all inputs connected)
1: Disconnected (at least one input is not connected)
Cumulative Counter Flag (Analog Input Terminals and Temperature Input
Terminals)
0: Normal
1: Error (monitoring set value exceeded)
Short-circuited Flag (Sensor Connector Terminals, Screw-less Clamp Input
and I/O Terminals, and Environment-resistive Input Terminals only), or
External Load Short-circuited Flag (Environment-resistive Output Termi-
nals, Sensor Connector Terminals, I/O Units only)
0: Normal I/O (all I/O points normal)
1: Short-circuited I/O (one or more I/O point short-circuited)
Unit Error Flag (Analog Input Terminals and Temperature Input Terminals)
0: Normal
1: Error (Data conversion stopped during to error in Unit.)
15
DRT2-series Slave
15
Master CPU Unit
14
IN Area
13
Status
Real inputs (e.g., 16 points)
8
7
1
0
Contents
Node address 1
Status: 8 points
0
See note 1.
Real inputs: 16 points
Section 3-2
37