SU2200RMXLTNET APC, SU2200RMXLTNET Datasheet - Page 44

no-image

SU2200RMXLTNET

Manufacturer Part Number
SU2200RMXLTNET
Description
UPS - Uninterruptible Power Supplies APC Smart-UPS XL 2200VA RM 5U 208V
Manufacturer
APC
Datasheet

Specifications of SU2200RMXLTNET

Power Rating
1600 W
Output Voltage Rating
208 V
Number Of Outlets
5
Interface Port
DB-9 RS-232, SmartSlot
Runtime (full Load)
10 min
Runtime (half Load)
34 min
Topology
Online
Tower / Rackmount
Rackmount
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
3. Refer to Figure 5-28. Connect the input wiring as shown. Secure
Connect Output Wiring to the Wire Harness Assembly
1. Locate the output panel from the hardwire kit (Figure 3-1,
2. Remove approximately 5 inches of outer jacket from the end of the
3. Repeat step 2 for the 120V output cable.
4. Connect the 208V and 120V output wiring to the wiring harness
42
the ground wire (green) to the primary ground connection with a
green ground screw from the hardware bag.
item #5) and remove the appropriate knockouts for the circuit
breaker and the output cable. Install a cable clamp so that it can be
tightened from the outside of the unit once the panel is installed.
208V output cable. Separate the three wires (white, black and
green.) Strip the insulation from the end of each wire so that ap-
proximately 3/8" of bare wire is exposed. Route the output wiring
through the output panel so that the panel can be installed cor-
rectly after the connections have been made. Make sure that the
cable clamp is installed such that the screws will be located outside
of the unit.
as shown in Figure 5-28. Secure each ground wire (green) to a
ground hole with a green ground screw from the hardware bag.

Related parts for SU2200RMXLTNET