Specifications of E5GN-C1LD-C AC/DC24

Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Svhc
No SVHC (15-Dec-2010)
Accuracy
±0.3 Of PV
Approval Bodies
CE, CSA
Approval Category
UL Recognised
Colour
Black
External
RoHS Compliant
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
*1. With set values 1, 4 and 5, the upper and lower limit values can
*2. Set value: 1, Upper- and lower-limit alarm
*3. Set value: 4, Upper- and lower-limit range
*4. Set value: 5, Upper- and lower-limit with standby sequence
0
1 *1
2
3
4 *1
5 *1
6
7
8
9
10
11
12
13
Case 1
Case 1
Set value
H < 0, L > 0
H < 0, L > 0
H < L
H < L
be set independently for each alarm type, and are expressed as
“L” and “H.”
For Upper- and Lower-Limit Alarm Described Above
• Case 1 and 2
• Case 3: Always OFF
L
L
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
H SP
H
SP
Alarm function OFF
Upper- and lower-limit
Upper-limit
Lower-limit
Upper- and lower-limit range
Upper- and lower-limit with
standby sequence
Upper-limit with standby sequence
Lower-limit with standby sequence
Absolute-value upper-limit
Absolute-value lower-limit
Absolute-value upper-limit with
standby sequence
Absolute-value lower-limit with
standby sequence
LBA (alarm 1 type only)
PV change rate alarm
Case 2
Case 2
SP
H > 0, L < 0
SP
H > 0, L < 0
H > L
H > L
L
L H
H
Alarm type
Case 3 (Always OFF)
Case 3 (Always ON)
H
H
H
H SP
L
L
SP
SP
SP
SP
SP
H
H
L
L
L
L
When alarm value
Output OFF
*5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
H < 0, L > 0
H > 0, L < 0
X is positive
H < 0, L > 0
H > 0, L < 0
H < 0, L < 0
H ≥ L
H ≤ L
H < 0, L < 0
H ≥ L
H ≤ L
0
0
0
0
Alarm output operation
L H
X
L H
L H
X
SP
SP
SP
SP
SP
SP
SP
X
X
X
X
X
X
---
---
When alarm value
*2
*3
*4
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
X is negative
*5. Set value: 5, Upper- and lower-limit with standby sequence
*6. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
*7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
*8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
X
X
SP
SP
SP
SP
X
X
X
X
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the operation of the standby sequence.
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the loop burnout alarm (LBA).
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the PV change rate alarm.
X
X
0
0
0
0
No alarm
Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
Set the upward deviation in the set point by setting
the alarm value (X).
Set the downward deviation in the set point by setting
the alarm value (X).
Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
A standby sequence is added to the upper- and
lower-limit alarm (1). *6
A standby sequence is added to the upper-limit alarm
(2). *6
A standby sequence is added to the lower-limit alarm
(3). *6
The alarm will turn ON if the process value is larger
than the alarm value (X) regardless of the set point.
The alarm will turn ON if the process value is smaller
than the alarm value (X) regardless of the set point.
A standby sequence is added to the absolute-value
upper-limit alarm (8). *6
A standby sequence is added to the absolute-value
lower-limit alarm (9). *6
*8
*7
Description of function
E5GN
11