E5GN-C1LD-C AC/DC24 Omron, E5GN-C1LD-C AC/DC24 Datasheet - Page 9

no-image

E5GN-C1LD-C AC/DC24

Manufacturer Part Number
E5GN-C1LD-C AC/DC24
Description
CONTROLLER, TEMP, 24AC/DC
Manufacturer
Omron
Datasheet

Specifications of E5GN-C1LD-C AC/DC24

Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Svhc
No SVHC (15-Dec-2010)
Accuracy
±0.3 Of PV
Approval Bodies
CE, CSA
Approval Category
UL Recognised
Colour
Black
External
RoHS Compliant
Specifications
Ratings
Power supply voltage
Operating voltage range
Power
consump-
tion
Sensor input
Input impedance
Control method
Control
outputs
Auxiliary
outputs
Event
inputs
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
Ambient operating humidity
Storage temperature
E5GN
Screw terminal
block
E5GN-@-C
Screwless clamp
terminal block
Relay output
Voltage output
(for driving SSR)
Current output
Number of outputs 1 or 2 max. (Depends on the model.)
Output
specifications
Number of inputs
External contact
input
specifications
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 5.5 VA (max.)
24 VAC/VDC: 3 VA/2 W (max.)
100 to 240 VAC: 5.5 VA (max.)
24 VAC/VDC: 3 VA/2 W (max.)
Models with temperature inputs
Models with analog inputs
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA
Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Relay output: SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum
applicable load: 5 V, 10 mA
2
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
Digital setting using front panel keys
11-segment digital display and individual indicators (7-segment display also possible)
Character height: PV: 7.5 mm, SV: 3.6 mm
Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial
communications.
Not supported
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic
operations, PV/SV status display, simple program, automatic cooling coefficient adjustment
25% to 85%
−25 to 65°C (with no condensation or icing)
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Voltage input: 0 to 50 mV
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
E5GN
9