E5@N/E5@N-H
Operation
Setting Levels Diagram
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
Basic Type
✽1. You can return to the operation level by executing a software reset.
✽2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
✽3. From the manual control level, key operations can be used to move to the operation level only.
✽4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN).
✽5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN)
Error Displays (Troubleshooting)
When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
Note: If the input value exceeds the display limit ( 1999 to 9999), though it is within the control range,
✽ These errors are displayed only when the PV/SP is displayed. Errors are not displayed for other displays.
s.err
e333
e111
Manual
mode
No.1 display
It can be done only by first turning OFF the power.
For details on the control range, refer to the E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156).
(E333)
(E111)
(S. Err)
Manual
Control Level
Start in manual mode.
above 9999. Under these conditions, control output and alarm output will operate normally.
✽3
Press the O Key or the
PF Key for at least 1 s. ✽4
Input error
A/D
converter
error
Memory
error
Meaning
a-m
Press the O Key
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)
Control stops.
Start in automatic mode.
Check the wiring of inputs for miswiring, disconnections, and short-circuits and check the
input type.
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
Press the PF Key
for at least 1 s.
Press the
O Key for
at least 1 s.
Press the O Key
for at least 1 s.
✽4
Operation
Level
Power ON
Initial Setting
Level
*1
PF Key
✽5
Advanced Function
Setting Level
Calibration Level
Press the
O Key less than 1 s.
Monitor/Setting
Item Level
Action
Input password while
amoV is displayed. (Set
value 169)
Input password.
c
Press the
O Key for less than 1 s.
25
100
Adjustment
Level
✽2
Press the O Key for at
least 3 s. (Display will flash
after 1st second.)
Communica-
tions Setting
Level
PF Key
✽5
Control in progress
Control stopped
Not displayed for some models
Level change
Press the
Keys for at
least 3 s.
(Display
will flash
after 1st
second.)
O+ M
will be displayed under 1999 and
Note: The time taken to
Control output
c
move to the protect
level can be adjusted
by changing the
“Move to protect level
time” setting.
100
OFF
OFF
OFF
25
Protect Level
Status at error
Operates as above
the upper limit.
Alarm output
Press the
Keys for at
least 1 s.
O+ M
OFF
OFF