PAXDR000 Red Lion Controls, PAXDR000 Datasheet - Page 27

no-image

PAXDR000

Manufacturer Part Number
PAXDR000
Description
AC, Dual Rate, Upgradeable Red
Manufacturer
Red Lion Controls
Type
Rate/Totalizerr
Datasheet

Specifications of PAXDR000

Accuracy
± (0.01% of Input Signal Frequency)
Cut Out, Panel
3.62W x 1.77H Inches
Dimensions
3.80W x 1.95H Inches
Display Digit Height
.56 Inches
Display Type
LED Adjustable
Function
Rate/Totalizer
Input Type
Switch Selectable Pulse
Keypad Type
3 Programmable Function (5 Keys Total)
Number Of Digits
Rate = 5, Totalizer = 8
Primary Type
Electronic
Range, Measurement
Rate = 0 to 99999, Totalizer = ±99999999
Special Features
Programmable Function Keys
Termination
Cage Clamp
Voltage, Supply
85 to 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
should be performed by qualified technicians using appropriate equipment.
Calibration does not change any user programmed parameters.
exiting Module 9. In this case, the existing calibration settings remain in effect.
Note: Allow a 30 minute warm-up period before starting calibration.
TROUBLESHOOTING
factory settings and display
memory failure or corrupted data. Immediately press RST key and reprogram
the meter. If the meter is powered down again before pressing the RST key, the
existing dynamic data will not be overwritten.

6.9 MODULE 9 - F
Intensity Level
PAR

Pressing the PAR and DSP keys at the same time on power-up will load the

When Analog Out recalibration is required (generally every 2 years), it
Calibration may be aborted by disconnecting power to the meter before
PROBLEM
NO DISPLAY
PROGRAM LOCKED-OUT
CERTAIN DISPLAYS ARE LOCKED OUT
INCORRECT DISPLAY VALUE or NOT
COUNTING
USER INPUT NOT WORKING CORRECTLY
OUTPUT DOES NOT WORK
JITTERY DISPLAY
MODULES or PARAMETERS NOT ACCESSIBLE
ERROR CODE (
SERIAL COMMUNICATIONS

9-FCS
d-LEV
Display
” DISPLAYED


RESTORE FACTORY DEFAULTS
is the Analog Output. If the meter appears to be indicating
incorrectly or inaccurately, refer to the Troubleshooting
section.
The meter will display
Press DSP key to return to the Display Mode. This will
overwrite all user settings with the factory settings.
using the arrow keys. The display will actively dim or
brighten as the levels are changed. This parameter also
appears in Quick Programming Mode when enabled.
DISPLAY INTENSITY LEVEL
The only item in the PAXDR meter that can be calibrated

Use the arrow keys to display
Enter the desired Display Intensity Level (0-15) by
Service Code
For further assistance, contact technical support at the appropriate company numbers listed.
Factory
COdE
CALIBRATION

)
. This allows operation in the event of a
Pro

and then return to
ACTORY

and press PAR.
REMEDIES
CHECK: Power level, power connections
CHECK: Active (lock-out) user input
ENTER: Security code requested
CHECK: Module 3 programming
CHECK: Input wiring, DIP switch setting, input programming, scale factor calculation,
CHECK: User input wiring, user input jumper, user input being used for signal, Module 2
CHECK: Corresponding plug-in card installation, output configuration, output wiring
CHECK: Wiring is per EMC installation guidelines, input signal frequency, signal quality,
CHECK: Lower input signal frequency, reduce scaling values (display capacity exceeded).
CHECK: Corresponding plug-in card installation, related controlling parameter selected
PRESS: Reset key (if unable to clear contact factory.)
CHECK: Wiring, connections, meter and host settings
PARAMETER MENU
input signal level, user input jumper, lower input signal frequency
scaling, update time, DIP switch setting
Divide by 0 condition exists for Display C calculation.
 
S
ERVICE
.
27
27
Analog Output Card Calibration
better (voltmeter for voltage output and/or current meter for current output) is
connected and ready. Then perform the following procedure:
1. Use the arrow keys to display
2.
3. Using the chart below, step through the five selections to be calibrated. At
4. When
Before starting, verify that a precision meter with an accuracy of 0.05% or

each prompt, use the PAXDR arrow keys to adjust the output so that the
external meter display matches the selection being calibrated. When the
external reading matches, or if the range is not being calibrated, press PAR.
SELECTION
O
   
 
   
   
  
is displayed. Use the arrow keys to select
  
PERATIONS
appears, press PAR twice and remove the external meters .
EXTERNAL METER
20.00
10.00
0.00
4.00
0.00

(
Adjust if necessary, press PAR
Adjust if necessary, press PAR
Adjust if necessary, press PAR
Adjust if necessary, press PAR
Adjust if necessary, press PAR

and press PAR.

ACTION
)
and press PAR.

Related parts for PAXDR000