W352-E1-06 Omron, W352-E1-06 Datasheet - Page 156

no-image

W352-E1-06

Manufacturer Part Number
W352-E1-06
Description
Product Manual
Manufacturer
Omron
Datasheet
I/O Check
Troubleshooting Flowcharts
IR 01003 output indicator
Check output device
SOL1.
Malfunction of SOL1
Check the voltage at the
IR 01003 terminals.
operating normally?
Operation OK?
Yes
Is the
Yes
Yes
No
No
power supply shorted
Disconnect the external wires
and check the conductivity of
each wire.
The I/O check flowchart is based on the following ladder diagram section.
Wire correctly.
Is output wiring
or overloaded?
Operation OK?
Is the external
correct?
No
Yes
No
No
Yes
00002
01003
(LS1)
Correct the short circuit
or limit the connected
load to the specified
range.
00003
(LS2)
SOL1 malfunction.
01003
Replace the CPU Unit,
Expansion Unit, or
Expansion I/O Unit with
the problem.
SOL1
Monitor the ON/OFF
status of IR 01003
with a Programming
Device.
Operation OK?
Yes
Section
No
A
To
next
page
137
5-5