Datasheet
Operation Procedure
Handling
Mount the EEPROM to the
CPM1-EMU01-V1.
Change the mode of the PC to PRO-
GRAM mode.
Connect the CPM1-EMU01-V1 to the
PC’s peripheral port.
After 2 or 3 s, check if the indicator is
lit green.
Press the DOWNLOAD TO PLC But-
ton.
Check if the indicator is blinking
green (indicating that downloading
has started).
Remove the Expansion Memory Unit
from the PC.
Check the program.
Check if the indicator is lit green
(indicating that downloading has
been successfully completed).
Yes
Yes
Yes
Start
End
No
No
No
See the note on
the right.
See the note above.
See the note above.
Mount the EEPROM to the
CPM1-EMU01-V1 before downloading.
Confirm the safety of the system.
Confirm the orientation of the connector
before connecting the CPM1-EMU01-V1.
Note
Before actual operation, check the contents
of the ladder program and the DM area, as
well as the expansion instruction settings.
• Is the connector properly con-
• Is the EEPROM properly mounted?
• Are the EEPROM specifications cor-
• Are the peripheral port communica-
If the indicator is not lit at all, lit red or
blinks red, downloading will not be
possible. In this case, check the fol-
lowing items.
nected?
rect?
tions settings correct?