EMC2303-1-KZ-TR SMSC, EMC2303-1-KZ-TR Datasheet - Page 62

no-image

EMC2303-1-KZ-TR

Manufacturer Part Number
EMC2303-1-KZ-TR
Description
Industrial Temperature Sensors RPM B Fan Controller w/HW Thermal Shutdwn
Manufacturer
SMSC
Datasheet

Specifications of EMC2303-1-KZ-TR

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Revision 0.32 (06-23-08)
1000 - 1001
1011 - 1111
FREQ[3:0]
RAN[3:0]
Example for PWM1 assigned to Zone 1:
In this case, the PWM1 duty cycle will be 50% at 50 ° C.
Since (Zone 1 Low Temp Limit) + (Zone 1 Range) = 50 ° C + 8 ° C = 58 ° C, the fan controlled by PWM1
will run at 100% duty cycle when the temperature of the Zone 1 sensor is at 58 ° C.
Since the midpoint of the fan control range is 54 ° C, and the median duty cycle is 75% (Halfway
between the PWM Minimum and 100%), PWM1 duty cycle would be 75% at 54 ° C.
Above (Zone 1 Low Temp Limit) + (Zone 1 Range), the duty cycle must be 100%.
The PWM frequency bits [3:0] determine the PWM frequency for the fan.
PWM Frequency Selection (Default =0011=29.3Hz)
Range Selection (Default =1100=32 ° C)
0000
0001
0010
0100
0101
1010
0000
0001
0010
0100
0101
0011
0110
0111
0011
0110
Zone 1 Low Temp Limit (Register 67h) is set to 50 ° C (32h).
Zone 1 Range (Register 5Fh) is set to 8 ° C (7h)
PWM1 Minimum Duty Cycle (Register 64h) is set to 50% (80h)
Table 8.27 Register Setting vs. Temperature Range
Table 8.26 Register Setting vs. PWM Frequency
DATASHEET
62
Fan Control Device with High Frequency PWM and Temperature Monitors
PWM FREQUENCY
29.3 Hz (default)
RANGE ( ° C)
~25 Khz
14.6 Hz
21.9 Hz
35.2 Hz
44.0 Hz
58.6 Hz
87.7 Hz
11.0 Hz
3.33
6.67
N/A
N/A
2.5
2
4
5
8
SMSC EMC2300
Datasheet