HDL36100 SQUARE D, HDL36100 Datasheet - Page 24

CIRCUIT BREAKER, THERMAL MAG, 3P, 100A

HDL36100

Manufacturer Part Number
HDL36100
Description
CIRCUIT BREAKER, THERMAL MAG, 3P, 100A
Manufacturer
SQUARE D
Series
PowerPactr
Type
Standardr
Datasheets

Specifications of HDL36100

Actuator Style
Toggle
No. Of Poles
3
Current Rating
100A
Voltage Rating Vdc
250V
Voltage Rating Vac
600V
Mounting Type
DIN Rail
Terminals
Lug
Actuator Type
Handle
Brand/series
HD Series
Characteristic
Adjustable Trip
Dimensions
6.40 (H) × 4.12 (W) × 4.36 (D) in.
Frame Type
H
Number Of Poles
3
Terminal Type
Line: Lug - Load: Lug
Voltage Rating
600/250 VAC/DC
Weight
5.00 lbs.
Wire Size
#14-3/0 AWG (Al/Cu)
Ampere Interrupting Ratings
25 k @ 240 VAC, 18k @ 480 VAC
Standards
UL489, CSA, NOM, IEC 60947, CE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
24
PowerPact
Section 1—General Information
Table 27:
1
UL 489
IEC
60947-3
2P devices use a 3P switch frame with the center pole inoperative.
Interrupting Performance
06/2010
Poles
Catalog Number
Withstand Ratings
AC Trip Point
Rated Insulation Voltage
Rated Impulse
Withstand Voltage
Rated Operational
Voltage
Frame
Automatic Molded Case Switch Specifications
®
H- and J-Frame Circuit Breakers
150 A
175 A
250 A
240 Vac 65 kA
480 Vac 35 kA
600 Vac 18 kA
250 Vdc 20 kA
ac
dc
Automatic Molded Case Switches
H-frame and J-frame circuit breakers are also available in automatic molded case switch construction.
Automatic switches are similar in construction to circuit breakers, except that the switches open
instantaneously at a factory-set non-adjustable trip point calibrated to protect only the molded case
switch itself.
Because of their molded case construction, they are more compact than conventional disconnect
switches and accept electrical accessories for added flexibility. Molded case switches are intended for
use as disconnect devices only.
UL 489 requires molded case switches to be protected by a circuit breaker or fuse of equivalent rating.
Molded case switches are labeled with their withstand ratings. The withstand rating of a switch is
defined as the maximum current at rated voltage that the molded case switch will withstand without
damage when protected by a circuit breaker or fuse with an equal or continuous current rating.
Table 28:
1
Poles
2
3
True 2P device. Others are a 2P in a 3P module.
2P
HGL26000S15 HGL3600S15 HLL26000S15 HLL36000S15 —
2250 A
750 Vac
8 kV
525 Vac
500 Vdc
Ampere
Rating
150 A
175 A
250 A
150 A
175 A
250 A
PowerPact H-Frame and J-Frame 250 A Unit-Mount Automatic Molded Case
Switches, 600 Vac with Factory Sealed Trip Unit (Suitable for Reverse Connection)
“G”
3P
65 kA
35 kA
18 kA
20 kA
2250 A
750 Vac
8 kV
525 Vac
500 Vdc
G Interrupting
Cat. No.
HGL26000S15
JGL26000S17
JGL26000S25
HGL36000S15
JGL36000S17
JGL36000S25
H-Frame
2P
125 kA
100 kA
50 kA
20 kA
750 Vac
8 kV
525 Vac
500 Vdc
2250 A
1
1
Trip Point Cat. No.
2250 A
3125 A
3125 A
2250 A
3125A
3125A
“L”
3P
125 kA
100 kA
50 kA
20 kA
2250 A
750 Vac
8 kV
525 Vac
500 Vdc
L Interrupting
HLL26000S15
JLL26000S17
JLL26000S25
HLL36000S15
JLL36000S17
JLL36000S25
2P
JGL26000S17 JGL36000S17 JLL26000S17
JGL26000S25 JGL36000S25 JLL26000S25
65 kA
35 kA
18 kA
20 kA
3125 A
750 Vac
8 kV
525 Vac
500 Vdc
1
Trip Point
2250A
3125 A
3125 A
2250 A
3125 A
3125 A
“G”
3P
750 Vac
65 kA
35 kA
18 kA
20 kA
3125 A
8 kV
525 Vac
500 Vdc
Terminal
AL150HD
AL175JD
AL250JD
AL150HD
AL175JD
AL250JD
© 2004–2010 Schneider Electric
J-Frame
2P
125 kA
100 kA
50 kA
20 kA
3125 A
750 Vac
8 kV
525 Vac
500 Vdc
1
Wire Range
14 AWG–3/0 AWG Al/Cu
4–4/0 AWG Al/Cu
3/0 AWG–350 kcmil Al/Cu
14 AWG–3/0 AWG Al/Cu
4–4/0 AWG Al/Cu
3/0 AWG–350 kcmil Al/Cu
All Rights Reserved
“L”
3P
JLL36000S17
JLL36000S25
125 kA
100 kA
50 kA
20 kA
3125 A
750 Vac
8 kV
525 Vac
500 Vdc