C200H-LK401 Omron, C200H-LK401 Datasheet - Page 49

no-image

C200H-LK401

Manufacturer Part Number
C200H-LK401
Description
PC LINK MODULE
Manufacturer
Omron
Datasheet

Specifications of C200H-LK401

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
46
SPECIAL I/O MODULES
HEAT/COOL TEMPERATURE CONTROL MODULES
Specifications
Note:
PART NUMBER
Current transformer detection
current
Input points (no. of loops)
Temperature control mode
No. of banks
Setting/Indication accuracy (see
note)
Hysteresis
Proportional band
Integral (reset) time
Derivative (rate) time
Control period
Sampling period
Input shift range
Internal current consumption
External supply voltage
Weight
Manual
C200H-TV00
C200H-TV10
The indication accuracy of thermocouples R and S at a temperature of 200 C max., that of thermocouples K and T at a temperature of --100 C max., and that of thermo-
couple U are all 4 C, 1 digit max. The indication accuracy of thermocouple B at temperature of 400 C or below is not guaranteed.


C200H-DSC01
Data Setting Console
C200H-TV00
0.1 to 49.9 A (with a heater burnout detecting current difference of 2.5 A min.), indication accuracy: 0.5% FS, 1 digit max.
Two points (two loops, each of which consists of a temperature sensor and CT)
PID, ON/OFF (selectable with a switch on the rear panel) (advanced PID with auto-tuning)
8 banks
digit max.
0.0 to 999.9 C/ F (in units of 0.1 C/ F)
0.0 to 999.9 C/ F (in units of 0.1 C/ F)
0 to 9,999 s (in units of 1 s)
0 to 9,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
500 ms
--99.9 to 999.9 C/ F (in units of 0.1 C/ F)
5 VDC, 0.33 A max. (supplied from the Backplane)
24 VDC
360 g max.
W240
0.5% of set (designated) value or 2 C whichever larger, 1
+10%

/
--15%
, 200 mA min.
Omron puts accurate heat/cool control right in the rack to make
advanced PID control with auto-tuning directly accessible on the
PLC rack. For applications requiring tight process control, such
as plastic extruders. Display and set parameters with the
C200H-DSC01 Data Setting Console.
Features
For stable temperature control, use advanced PID and an
auto-tuning feature. ON/OFF control can also be selected.
Dedicated Module available for each Temperature Sensor.
Two types of Temperature Control Module are available,
depending on the thermocouple or platinum resistance
thermometer temperature sensor used.
Comprehensive output specifications -- three types are
available: C200H-TV
C200H-TV
current output.
Two Heat/Cool Control loops with a single module
Heater burnout can be quickly detected -- a minimum current
difference of 2.5 A and a heater burnout detection setting
range of 0.1 to 49.9 A allows for the rapid correction.
Eight banks of data settings, such as set point (SP) and
alarm set values, can be preset in eight data banks for easy
selection.
Data Input and Display -- The C200H-DSC01 Data Setting
Console (sold separately) is used to input data and display
process values (PV) and set values (SV). The easy-to-read
display can be panel-mounted.
Data reading/writing User Program of the C200HX/HG/HE
allows reading or writing of various data.

C200H-TV10
digit max.
0.5% of set (designated) value or 1 C whichever larger, 1
2 for voltage output, and C200H-TV


1 for transistor output,

3 for

Related parts for C200H-LK401