CP2000AC54TEP Lineage Power, CP2000AC54TEP Datasheet - Page 14

Linear & Switching Power Supplies 2000W +/-54Vdc 37A Rectifier POE

CP2000AC54TEP

Manufacturer Part Number
CP2000AC54TEP
Description
Linear & Switching Power Supplies 2000W +/-54Vdc 37A Rectifier POE
Manufacturer
Lineage Power
Datasheet

Specifications of CP2000AC54TEP

Product
Linear
Output Power Rating
2000 W
Input Voltage
176 VAC to 275 VAC
Number Of Outputs
1
Output Voltage (channel 1)
54 VDC
Mounting Style
Plug In
Dimensions
13.85 in L x 4 in W x 1.63 in H
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
10/10 Compact Power Line Brochure
Integrated Monitoring Inputs/Outputs
• System plant voltage (accuracy ±0.5%, resolution 0.01V)
• One system shunt (accuracy ±1% full scale, resolution 1A)
• Up to 15 binary inputs
• Up to 5 user assignable Form-C output alarms (50VDC @ .3A)
• 1-Wire™ bus devices
General
Operating Voltage
Input Power
Operating Temperature Range
Storage Temperature Range
Operating Relative Humidity
Physical Specifications
Display
-
-
-
-
-
-
-
Battery or load
Mounted in the return side of DC bus
Six inputs close/open to battery
9 input close/open to return (number is dependent upon
number of output alarms)
User assignable
Up to 16 temperature probes (QS873)
Up to 6 mid-string monitors (ES771)
±24 Vdc, ±48 Vdc
(Range: ±18 to ±60 Vdc)
Less than 7W
-40°C to +75 °C (-40 to 167 °F)
-40°C to +85°C (-40 to 185 °F)
0 - 95% (non-condensing)
1.75 in. H, 0.75 in. W, 8.00 in. D; 0.5lb
45mm H, 20mm W, 204mm D; 227g
8-line by 40-character backlit LCD
© 2010 Lineage Power. All rights reserved.
Galaxy Manager Compatible
• Centralized web server and database with multiple user access
• Monitor and control of more than 40 connected devices
• Management information from polling or alarms received from
• Trend user selected data over time
• Automatic or manual report generation
• Standard engineering tools like reserve time calculators and
Agency Certifications
Radiated Emissions
Safety
RoHS
EMC
ESD
to live or managed data with drill down to problem details
alarm traps from multiple sites are available on one screen via
the inter/intranet
cable voltage drop analyzer
T E C H N I C A L S P E C I F I C A T I O N S - C ON T RO L L E R
FCC, Class B; EN 55022, Class B
UL Unlisted Component as Part of CPL or SPS
Power System
Compliant to RoHS EU Directive 2002/95/EC
FCC/EN55022 Class B, CISPR22 Level B
EN 61000-4-2 level 4
Page 14