CP2000AC54TEP Lineage Power, CP2000AC54TEP Datasheet - Page 20

Linear & Switching Power Supplies 2000W +/-54Vdc 37A Rectifier POE

CP2000AC54TEP

Manufacturer Part Number
CP2000AC54TEP
Description
Linear & Switching Power Supplies 2000W +/-54Vdc 37A Rectifier POE
Manufacturer
Lineage Power
Datasheet

Specifications of CP2000AC54TEP

Product
Linear
Output Power Rating
2000 W
Input Voltage
176 VAC to 275 VAC
Number Of Outputs
1
Output Voltage (channel 1)
54 VDC
Mounting Style
Plug In
Dimensions
13.85 in L x 4 in W x 1.63 in H
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
10/10 Compact Power Line Brochure
J2007001 Shelves System Controller
Communication Signals for J2007001 Shelves
• J1 provides alarm outputs and inputs based on the controller installed (see
• J2 provides alarm inputs (see table below). Alarm inputs are contact
• J3 battery thermal probe (QS873A) or battery mid-string voltage monitor
• J4 shelf to shelf communication connection
• J5 LAN/Ethernet.
• J7 provides distribution control for shelves with external distribution. See
Battery Monitoring
Temperature/Voltage probes are needed for battery monitoring. They
are connected to each battery or battery string to provide slope thermal
compensation, temperature alarms and voltage imbalance alarms. Refer to
ordering guide for diagram and part numbers.
Several versions of the CP841A Pulsar Edge controller are available. Each offers different alarm input/outputs on the
J1 connector of the shelf.
CP841A_9C0R
CP841A_3C3R
CP841A_0I5R
J1 CONNECTOR – Pin Out
1
2
3
4
5
6
7
8
9
10
table below). Inputs are “Dry”, no voltage, contact Closures or Opens to
a common return on pin 6. Outputs are relay contacts. Both input and
output alarms are customer defined on the controller’s web pages.
Closures or Opens to the non-grounded side of the dc bus [-48V]. Pins 6, 7,
8 provide -48V for these alarm inputs.
(ES771) with battery thermal probe.
table below.
Pin
Signals for SPS841A_3C3R
ALM1 Input
ALM2 Input
Alarm Relay 1 Rtn
Power Minor Rtn
Power Major Rtn
ALM1, 2, 6C RTNS
ALM6 Input
Alarm Relay 1
Power Minor
Power Major
J1 has 9 alarm inputs with a common return and no output relays
J1 has 3 alarm inputs with a common return and 3 output relays; Power Major, Power Minor, 1 Selectable
J1 has 0 alarm inputs and 5 output relays; Power Major, Power Minor, 3 Selectable
Signals for SPS841A_0I5R
Alarm Relay 3 Rtn
Alarm Relay 2 Rtn
Alarm Relay 1 Rtn
Power Minor Rtn
Power Major Rtn
Alarm Relay 3
Alarm Relay 2
Alarm Relay 1
Power Minor
Power Major
© 2010 Lineage Power. All rights reserved.
J2 CONNECTOR
Pin
1
2
3
4
5
6
7
8
ORDERING INFORMATION – COMPACT POWER LINE
Signal
ALM6 Input
-
ALM3 Input
ALM4 Input
ALM5 Input
-48V
-48V
-48V
J7 CONNECTOR
Pin
1
2
3
4
5
6
7
8
9
10
Signal
FAJ
Coil Rtn
LVD_NC
LVD_NO
Shunt-
OS
Coil1
Coil2
LVD Status Rtn
Shunt+
Page 20