System Setup
220
1, 2, 3...
tween the PC and the CVSS. These settings are for the CVSS and must agree
with the settings for the PC (see the following).
To change a parameter, select the item and then specify the desired settings on
the display that will appear. The parameters and their possible settings are de-
scribed in the following table.
Follow the procedures mentioned below to connect the host interface port on the
PC’s CPU and the computer.
Port
Baud rate
Unit #
Parity
Data bits
Stop bits
Comm watch
time
1. Set the transmission path selector on the CPU to RS-232C and turn ON pin
2. Connect the computer running CVSS to the CPU’s host interface port.
3. Select ASCII from the offline system setup menu and set the communica-
4. Set DIP switch 4 on the CPU to OFF. Then adjust the communications speci-
Parameter
4 of the DIP switch on the CPU to automatically set the following parame-
ters:
Baud rate:
Parity:
Data length:
Stop bits:
tions mode to 1. Adjust the communications specifications to the above set-
tings in the online mode. Then return to the offline mode.
fications to the above settings in the offline mode to allow the PC to commu-
nicate online with the computer.
The computer port to which the PC is
connected.
The transmission speed.
The unit number of the PC for
communications via the host interface.
The parity to be used for checking
transmissions.
The data length to be used.
The number of stop bits to be used.
The monitoring time for responses
from the PC. An error will be
generated if the PC does not respond
within the specified time.
7 bits
4,800 bps
Even
2
Function
COM1 or COM2
Set to the value that has
been set with the DIP
switches on the front of
the PC’s CPU.
00 to 31
Even, odd, or no parity
7 or 8 bits
1 or 2 bits
2 to 60 s
Possible settings