11-2-3 Network Power Voltage Monitor
Description
Settings Using the CX-Integrator
Functions Common to All Slave Units
1,2,3...
Note
Fault Action
Idle Action
5. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
6. Click the OK Button and exit the window.
The Network Power Voltage Monitor function stores the present value, mini-
mum value, and maximum value of the network power voltage in the Slave
Unit memory. If a monitor voltage is set using the CX-Integrator, the monitor
voltage is stored in the Slave Unit memory. (The default is 14 V.) If the voltage
drops below the monitor voltage, a flag in a status area in the Slave Unit will
turn ON to notify the Master Unit. The notification details can be read using
the CX-Integrator or using explicit messages.
1. Turn ON the power to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
(1) The minimum communications power voltage for the CompoNet network
(2) The maximum and minimum values of the network power voltage are
A communications error occurs when communications with the Master
Unit are interrupted.
Idle action is the status that results when an idle output specification is re-
ceived from the Master Unit. An idle output is specified when a CPU Unit
monitoring error occurs in a CS/CJ-series Master Unit.
download the data, and then click the Reset Button to reset the Unit.
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
Clear
Hold
Clear
Hold
itself is 14 V, so if the network power voltage drops below 14 V, it may not
be possible to read a measurement value using the CX-Integrator.
cleared when the network power is turned OFF.
Clears all output data from the Master Unit to 0 when a communica-
tions error occurs.
Holds all output data from the Master Unit at its current status when a
communications error occurs.
Clears all output data from the Master Unit to 0 when idle action occurs.
Holds all output data from the Master Unit at its current status when idle
action occurs.
Section 11-2