11-5-3 Cumulated Count
Description
Setting Using the CX-Integrator
Analog I/O Slave Unit (output) Functions
1,2,3...
Note The following table shows the divisions for the cumulated counter.
The cumulated count calculates an approximation to the integral of analog
output values over time. The cumulated value can be calculated in “count
hours” (by selecting “hours”) or “count minutes” (by selecting “minutes”). The
count value is the analog output value in the industry unit obtained after scal-
ing. For example, 100.0 count hours indicates a value equivalent to an analog
output value of 100 counts continuing for one hour. The counter range for a
two-word area (four bytes) for count hours or count minutes is –214,748,364.8
to 214,748,364.7. Data is displayed on the CX-Integrator in units of 0.1 hours
or minutes.
Monitor values can be set in the Slave Unit. When the cumulated count value
exceeds the set monitor value, the Cumulated Counter Flag in the area for
Generic Status Flags turns ON.
1. Turn ON the power supply to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
3. Select the tab page for the output where the cumulated counter is to be set,
Analog output value
Hour
Minute
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
and select the Cumulated Count Check Box under the Function Choice
heading.
Unit
Division width
(See note.)
3.6 s (1/1,000 hour)
60 ms (1/1,000 minute)
Cumulated value
(count × hour or minute)
Divisions
Time t
Section 11-5
537