Temperature Input Unit Functions
11-6-10 Input Error Detection Disable Function
Description
560
1,2,3...
Note
6. Click the OK Button. The Edit Calculation Data Window will close.
7. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
8. Click the OK Button and exit the window.
If there are inputs that are not being used, input error detection (including off-
wire detection) can be disabled. If this function is used, the Temperature Input
Warning Flag and Off-wire Detection Flags will be OFF regardless of the con-
nection status of the input sensor or temperature range.
When this function is enabled, the temperature data is set to 7FFF hex (7FFF
FFFFF when 1/100 Display Mode is being used).
1. Turn ON the power supply to the Temperature Input Unit.
2. Double-click the icon of the Temperature Input Unit to be set in the Network
3. Click the tab for the input where the input error detection disable function
4. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
5. Click the OK Button and exit the window.
Use this function only if there are unused inputs. If this function is used while a
sensor is connected, it will not detect input errors (including disconnections).
download the data, and then click the Reset Button to reset the Unit.
Configuration Window or right-click the icon and select Parameter - Edit.
The Configuration Window will be displayed.
is to be set, and select the Disable Input Error’s Detection Check Box in the
Function Choice Area.
download the data, and then click the Reset Button to reset the Unit.