11-3-3 Error Prevention for Surge Current at Startup (Input Units Only)
Description
Settings Using the CX-Integrator
Functions of Digital I/O Slave Units
1,2,3...
4. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
5.
This function can be used to prevent reading inputs while the I/O power is
OFF and for 100 ms after the I/O power is turned ON (i.e., until the Slave Unit
stabilizes). It helps avoid input errors caused by inrush current from con-
nected devices when the I/O power supply is turned ON. This function is
enabled or disabled by the CX-Integrator or by explicit messages.
1. Turn ON the power supply to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
3. Click the IN Tab, and select Enable for the Sensor Power ON Delay.
download the data, and then click the Reset Button to reset the Unit.
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
Click the OK Button and exit the window.